Division of Petroleum & Chemical Safety

 

Facility: 2025054 Tank: 9

Click for Facility/Tank Ownership history

Capacity: 4000
Product: E85
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 9/6/2023
Current Age: 0
Install Date: 6/29/2023
Last Used Date:
Product Date: 8/17/2023
Petroleum Use:
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number G-03360043

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/28/2023 8/28/2023 8/28/2024
Leak Detect - Tank Automatic Tank Gauging Red Jacket Pro Max 9/6/2023 9/6/2023 9/6/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 9/6/2023 9/6/2023 9/6/2024
Overfill Prev Device Overfill Drop Tube Valve 9/6/2023 9/6/2023 9/6/2026
Piping Flexible Double Wall NUPI Smartflex 8/28/2023 N/A N/A
Piping Single Wall STP/Tanktop Sump 9/6/2023 9/6/2023 9/6/2026
Leak Detect - Piping Sump Sensor with positive shutdown 9/6/2023 9/6/2023 9/6/2024
Spill Contain Device Double Wall Spill Bucket 9/6/2023 9/6/2023 9/6/2026
Tank Fiberglass Double Wall XERXES 6/29/2023 N/A N/A

Latest Blended Fuel Compatibility Form

File Name Status Status Date
CompatibilityFormSummary06272023-065933.pdf Approved 6/27/2023

Compatibility Form Attachments

File Name Description
vr-probe.pdf ATG probe
Equipment-Compatibility.pdf Dispenser
SealantReferenceGuide.pdf Dope
577013-465.pdf Electronic Pressurized Line Leak Detection
UGPetroleumStorageTankWarr.5.1.2019.pdf Fiberglass Double Wall
20230626123015644.pdf Fill Adoptor /fill cup
Ethanol Compatibility.pdf Flexible Double Wall
Equipment-Compatibility.pdf Hose
20230626131604315.pdf Interstitial sensor
20230525163930680 (1).pdf Non-Discriminating Sump Sensor with positive shutdown
APROBACION UL CONTENEDORES DOBLE PARED 2019.pdf Not Installed UDC Sump
Equipment-Compatibility.pdf Nozzle
20230525161811464.pdf Overfill Drop Tube Valve
opw-10-series-emergency-shut-off-valves-2018.pdf Shear Valve
20230525161811464.pdf Single Wall Spill Bucket
APROBACION UL CONTENEDORES DOBLE PARED 2019.pdf Single Wall STP/Tanktop Sump
red-jacket-stp-ag-spec-sheet.pdf Submersible Turbine Pump

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Flexible Double Wall NUPI Smartflex Precision Test Pass 8/28/2023 Show History
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 8/28/2023 Show History