Division of Petroleum & Chemical Safety

 

Facility: 2012027 Tank: 1

Click for Facility/Tank Ownership history

Capacity: 10000
Product: Diesel Fuel
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 4/4/1986
Current Age: 45
Install Date: 4/1/1979
Last Used Date:
Product Date:
Petroleum Use: None
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/12/2021 12/6/2023 12/6/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 12/6/2023 12/6/2024
Overfill Prev Device Overfill Drop Tube Valve 6/7/2022 6/7/2025
Piping Fiberglass Double Wall 6/25/2021 N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Single Wall STP/Tanktop Sump 8/8/2018 6/24/2021 6/24/2024
Leak Detect - Piping Sump Sensor with positive shutdown 12/6/2023 12/6/2024
Spill Contain Device Single Wall Spill Bucket 2/18/2020 6/7/2022 6/7/2025
Tank Fiberglass Single Wall N/A N/A

Latest Blended Fuel Compatibility Form

No Compatibility Forms Listed


Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Fiberglass Double Wall Precision Test Pass 12/6/2023 Show History
Piping Fiberglass Single Wall Piping Precision Test Pass 6/25/2021 Show History
Piping Flexible Single Wall Piping in Chase Precision Test Pass 5/7/2020 Show History