Division of Petroleum & Chemical Safety

 

Facility: 1006629 Tank: 5

Click for Facility/Tank Ownership history

Capacity: 10000
Product: B-99
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 12/4/2007
Current Age: 16
Install Date: 9/27/2007
Last Used Date:
Product Date: 9/27/2007
Petroleum Use:
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Fiberglass Non-Corrosive 7/25/2007 N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive 7/25/2007 N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/7/2022 4/11/2024 4/11/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 7/25/2007 4/11/2024 4/11/2025
Overfill Prev Device Overfill Drop Tube Valve 9/7/2022 9/7/2022 9/7/2025
Piping Fiberglass Double Wall Ameron 7/25/2007 N/A N/A
Piping Flex Connector Steel N/A N/A
Piping Single Wall STP/Tanktop Sump 4/17/2019 4/13/2022 4/13/2025
Leak Detect - Piping Sump Sensor 4/11/2024 4/11/2025
Spill Contain Device Single Wall Spill Bucket 7/25/2007 4/13/2022 4/13/2025
Tank Fiberglass Single Wall Containment Solutions 7/25/2007 N/A N/A

Latest Blended Fuel Compatibility Form

File Name Status Status Date
CompatibilityFormSummary10032022-150949.pdf Approved 10/3/2022

Compatibility Form Attachments

File Name Description
10 3 22 Veeder Root Probe Sensor10032022.pdf ATG Probe
10 3 22 Ameron10032022.pdf Fiberglass Double Wall
10 3 22 containment solutions 10032022.pdf Fiberglass Single Wall
10 3 22 OPW10032022.pdf Flex Connector Steel
10 3 22 Vaporless10032022.pdf Mechanical Pressurized Line Leak Detection
10 3 22 Veeder Root sump sensor10032022.pdf Non-Discriminating Sump Sensor in Single Wall STP/Tanktop Sump
10 3 22 OPW10032022.pdf Overfill Drop Tube Valve
10 3 22 OPW10032022.pdf Single Wall Spill Bucket
10 3 22 OPW10032022.pdf Single Wall STP/Tanktop Sump
10 3 22 Veeder Root 10032022.pdf Submersible Pump

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Fiberglass Double Wall Ameron Precision Test Pass 4/11/2024 Show History
Tank Fiberglass Single Wall Containment Solutions Precision Test (Tank) Pass 5/11/2023 Show History