Division of Petroleum & Chemical Safety

 

Facility: 2006920 Tank: 3

Click for Facility/Tank Ownership history

Capacity: 8000
Product: E85
Status: Currently in use
Regulated Status Federal
OSFM First Notify Date: 4/25/1986
Current Age: 54
Install Date: 1/1/1970
Last Used Date:
Product Date: 1/1/1970
Petroleum Use:
CERCLA Substance:
CAS Code:
Removed Date:
Abandoned Material:
Abandoned Date:
Red Tag Issue Date:
Fee Due: $0.00
UL Number

Equipment Information

Equipment Type Equipment Install Date Last Passing Test Date Test Expire Date Failed Test Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 5/30/2023 5/30/2026
Corrosion Prot - Tank Lining Materials Internal Bridgeport Chemical Glass Armor GA 27P 7/1/2002 3/4/2021 3/4/2026
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/5/2023 9/5/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/30/2023 5/30/2024
Overfill Prev Device Overfill Drop Tube Valve 8/31/2023 8/31/2023 8/31/2026
Piping Fiberglass Single Wall Piping A.O. Smith 9/5/2023 N/A N/A
Piping Single Wall STP/Tanktop Sump 8/31/2023 8/31/2023 8/31/2026
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Double Wall Spill Bucket 8/31/2023 8/31/2023 8/31/2026
Tank Fiberglass Single Wall N/A N/A

Latest Blended Fuel Compatibility Form

File Name Status Status Date
CompatibilityFormSummary09072023-105531.pdf Approved 9/7/2023

Compatibility Form Attachments

File Name Description
Veeder Root E85 probe 577013-054.pdf ATG Probe
Veeder Root E85 probe 577013-054.pdf ATG Probe
WAYNE MH1821-45-6 Ovation CertificateofCompliance.pdf Dispenser
WAYNE MH1821-45-6 Ovation CertificateofCompliance.pdf Dispenser
OPW Belowground Product Compatibility Listing 071518.pdf Double Wall Spill Bucket
Veeder Root PLLD.pdf Electronic Pressurized Line Leak Detection
Veeder Root PLLD.pdf Electronic Pressurized Line Leak Detection
Owens Corning 4-14-95 document on alcohol warranties by date.pdf Fiberglass Single Wall
Owens Corning 4-14-95 document on alcohol warranties by date.pdf Fiberglass Single Wall
Flexing Compatibility Statement.pdf Flex
Flexing Compatibility Statement.pdf Flex
Goodyear E85 Ethanol hose.pdf Hose
Goodyear E85 Ethanol hose.pdf Hose
bridgeport tank lining.pdf Lining Materials Internal
bridgeport tank lining.pdf Lining Materials Internal
OPW 11a-and-11b-automatic-nozzles.pdf Nozzle
OPW 11a-and-11b-automatic-nozzles.pdf Nozzle
OPW 71SOM_Overfill_Prevention_Valve.pdf Overfill Drop Tube Valve
OPW 71SOM_Overfill_Prevention_Valve.pdf Overfill Drop Tube Valve
Gasoila E-Seal.pdf PIPE DOPE
OPW 10_Plus_Series_Emergency_Shut-Off_Valves.pdf Shear Valve
OPW 10_Plus_Series_Emergency_Shut-Off_Valves.pdf Shear Valve
Ameron Pipe Compatibility Statement.pdf Single wall Fiberglass piping
Bravo Sump Compatibility Statement.pdf Single Wall UDC Sump
Bravo Sump Compatibility Statement.pdf Single Wall UDC Sump
Bravo Sump Compatibility Statement.pdf STP/Tanktop Sump
FE PETRO STPAPM200-VL2 ffs-0412-60-hz-advanced-protection-submersible-turbine-pumps-datasheet.pdf Submersible Turbine Pump
FE PETRO STPAPM200-VL2 ffs-0412-60-hz-advanced-protection-submersible-turbine-pumps-datasheet.pdf Submersible Turbine Pump

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date History
Piping Fiberglass Single Wall Piping A.O. Smith Precision Test Pass 9/5/2023 Show History
Tank Fiberglass Single Wall Precision Test (Tank) Pass 3/5/2021 Show History