Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7044864
Status: Active
Facility Name: Ninkasi Beverage Group, LLC d/b/a Marketplace - Shell
Address: 2301 Reed Station Parkway
Carbondale, IL 62901
County: Jackson
Property Parcel: 15-13-126-006
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y004245
Green Tag Issue Date: 9/5/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Ninkasi Investment, LLC
Owner Address: 514 S. Illinois Ave.
Carbondale, IL 62901
Owner Status: Current Owner
Purchase Date: 8/29/2018
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/12/2023

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/24/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039280 Ninkasi Investment, LLC Current Owner 8/29/2018
U0036053 HBA Development Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00161-2024UPG Upgrade Approved / Issued 2/9/2024 2/10/2024 8/12/2024 Documents

Deficiencies (Current)

NOV Number: E0020241035 (Pending)    Issue Date: 4/9/2024    Expiration Date: 6/8/2024    View NOV Form

Tanks Deficiency
1, 2 Miscellaneous - Must have dispenser sump hydrostatically tested and repaired or replaced if needed
1, 2 Precision line test required. - Must test both product lines feeding Disp 9/10 due to dispenser being hit by car.
1, 2 Shear valve(s) not in proper working order. - Repair broken shear valve(s) under dispenser 9-10.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/12/2011 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 7/8/2011 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/5/2024 2/5/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 with CSLD 2/5/2024 2/5/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/5/2024 2/5/2025
Overfill Prev Device Overfill Drop Tube Valve 2/7/2022 2/7/2025
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 2/7/2022 2/7/2025
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2024 2/5/2025
Spill Contain Device Single Wall Spill Bucket 2/7/2022 2/7/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test Pass 2/5/2024



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/12/2011 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 7/8/2011 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/5/2024 2/5/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 with CSLD 2/5/2024 2/5/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/5/2024 2/5/2025
Overfill Prev Device Overfill Drop Tube Valve 2/7/2022 2/7/2025
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 2/7/2022 2/7/2025
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2024 2/5/2025
Spill Contain Device Single Wall Spill Bucket 2/7/2022 2/7/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test Pass 2/5/2024



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/12/2011 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 7/8/2011 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/5/2024 2/5/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 with CSLD 2/5/2024 2/5/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/5/2024 2/5/2025
Overfill Prev Device Overfill Drop Tube Valve 2/7/2022 2/7/2025
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 2/7/2022 2/7/2025
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2024 2/5/2025
Spill Contain Device Single Wall Spill Bucket 2/7/2022 2/7/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test Pass 2/5/2024



Tank Number 4

Capacity: 6000 Petroleum Use:
Product: Gasoline - Non Ethanol CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 7/12/2011 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 7/8/2011 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/14/2024 2/14/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 with CSLD 2/5/2024 2/5/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/5/2024 2/5/2025
Overfill Prev Device Overfill Drop Tube Valve 2/7/2022 2/7/2025
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 2/7/2022 2/7/2025
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2024 2/5/2025
Spill Contain Device Single Wall Spill Bucket 2/7/2022 2/7/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test Pass 2/14/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/7/2022 2/7/2025
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2024 2/5/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/7/2022 2/7/2025
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2024 2/5/2025



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/7/2022 2/7/2025
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2024 2/5/2025



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/7/2022 2/7/2025
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2024 2/5/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/7/2022 2/7/2025
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2024 2/5/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/7/2022 2/7/2025
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2024 2/5/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/7/2022 2/7/2025
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2024 2/5/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/7/2022 2/7/2025
Leak Detect - Piping Sump Sensor with positive shutdown 2/5/2024 2/5/2025

MFD Motorfuel Dispensing Forms

No Forms Found