Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 7039708
Status: Active
Facility Name: KBJ's Truck Stop
Address: 10894 Bridgeport Rd.
Bridgeport, IL 62417
County: Lawrence
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002545
Green Tag Issue Date: 11/30/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Jagruti Patel
Owner Address: 10894 Bridgeport Rd.
Bridgeport, IL 62417
Owner Status: Current Owner
Purchase Date: 5/1/2017
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/27/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/1/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039064 Patel, Jagruti Current Owner 5/1/2017
U0034234 L E Anderson Bros. Oil, Inc. Former Owner 8/9/2000
U0000619 L.E. Anderson Brothers Oil Company, Inc. Former Owner 6/8/2000
U0029463 Bell, Chuck Former Owner 6/8/2000
U0035804 Patel, Vikram Kumar Former Owner
U0033836 Kirit Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240568 (Pending)    Issue Date: 2/28/2024    Expiration Date: 4/28/2024    View NOV Form

Tanks Deficiency
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

NOV Number: E0020240570 (Pending)    Issue Date: 2/28/2024    Expiration Date: 4/28/2024    View NOV Form

Tanks Deficiency
4, 5, 6 Line interstitial sensors have been raised and rendered inoperational. - Diesel STP containment sump sensor raised out of liquid. Remove liquid and lower sensor. Dispenser 1/2 sump sensor raised and must be lowered to be in contact with the bottom of the sump.
Facility Missing copies of 30 day Walkthrough Inspection Report. - No inspection reports completed.
Facility Missing copies of current testing certificates for operator training - At least one person onsite has to be trained in UST Class C at all times at an attended facility. The person on site does not have class C training completed.
Facility Missing list of designated Class A/B & C Operators - Update list.
6 Piping sump tested triennially using low level positive shut off option. Sump does not meet low level test requirements. See remarks. Perform standard hydrostatic test on sump. - Diesel STP sump sensor raised out of liquid.
4, 6 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
6 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Diesel STP sump.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline Removed Federal $0.00 06/20/2000 - REM
2 10000 Gasoline Removed Federal $0.00 06/20/2000 - REM
3 10000 Diesel Fuel Removed Federal $0.00 06/20/2000 - REM
4 10000 Gasoline - Regular Currently in use Federal $0.00
5 10000 Gasoline - Premium Currently in use Federal $0.00
6 10000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9 Active
Sat Active

MFD Motorfuel Dispensing Forms