Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 7032963
Status: Inactive
Facility Name: Ropers Shawnee Mart, Inc.
Address: 1098 Eddyville Blacktop
Eddyville, IL 62928
County: Pope
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: U004406
Green Tag Issue Date: 10/16/2019
Green Tag Expiration Date: 12/31/2021

Owner Details

Owner Name: Ropers Shawnee Mart, Inc.
Owner Address: 117 Saddle Dr.
Stonefort, IL 62987
Owner Status: Current Owner
Purchase Date: 5/1/2012
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/16/2020

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 10/16/2019 12/31/2021

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036585 Ropers Shawnee Mart, Inc. Current Owner 5/1/2012
U0034176 Hill's Shawnee Mart, Inc. Former Owner 8/1/2006
U0031196 Wilson, Ray Former Owner 3/15/2002
U0030426 Bates, Douglas & Donna Former Owner 3/15/2002
U0022712 Hicks Randall & Peggy Former Owner 5/16/1994
U0035693 Spirits, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020202876 (Referred to Legal)    Issue Date: 10/2/2020    Expiration Date: 12/1/2020    View NOV Form

Tanks Deficiency
1, 2 Submit Notification Form For Tank Status Change - Must submit a Notification Form showing tanks out of service and the last date used.

NOV Number: E0020212707 (Referred to Legal)    Issue Date: 10/7/2021    Expiration Date: 12/6/2021    View NOV Form

Tanks Deficiency
Facility Financial responsibility must be reported yearly

NOV Number: E0020230128 (Referred to Legal)    Issue Date: 1/12/2023    Expiration Date: 3/13/2023    View NOV Form

Tanks Deficiency
Facility Financial responsibility must be reported yearly - https://sfm.illinois.gov/
Facility Submit Notification Form For Ownership Change - https://sfm.illinois.gov/
1, 2 Tank sacrificial anode system not tested (Required every 3 years). - Cathodic protection testing was due on 6-10-22, if a passing test is not conducted by 3-13-23 a removal violation will be issued per (41 Ill. Adm. Code 175.810(b)).

NOV Number: E0020230750 (Referred to Legal)    Issue Date: 3/23/2023    Expiration Date: 5/22/2023    View NOV Form

Tanks Deficiency
1, 2 Remove tank(s) - Corrosion Protection not Maintained - Tank corrosion protection expired on 6-10-22. A violation was written on 1-12-23 to have corrosion protection tested and provide passing results. Tank corrosion testing has not been performed.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Out of service CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/16/1994 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 5/20/1994 Red Tag Issue Date: 3/19/2021
Last Used Date: 10/2/2020 Fee Due: $0.00
Product Date: 5/24/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 3/25/2024 3/25/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/12/2024 4/12/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 4/12/2024 4/12/2025
Overfill Prev Device Ball Float Vent Valve OPW 53 4/12/2024 4/12/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/12/2024 4/12/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 4/12/2024
Tank STIP3 Single Wall Precision Test (Tank) Pass 4/12/2024



Tank Number 2

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Out of service CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/16/1994 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 5/20/1994 Red Tag Issue Date: 3/19/2021
Last Used Date: 10/2/2020 Fee Due: $0.00
Product Date: 5/24/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 3/25/2024 3/25/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/12/2024 4/12/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 4/12/2024 4/12/2025
Overfill Prev Device Ball Float Vent Valve OPW 53 4/12/2024 4/12/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 4/12/2024 4/12/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 4/12/2024
Tank STIP3 Single Wall Precision Test (Tank) Pass 4/12/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found