Notice of Violations (Current)
NOV Number:
E0020201738
(Referred to Legal)
Issue Date:
7/9/2020
Expiration Date:
9/7/2020
View NOV Form
Tanks |
Violation |
3 |
Tank monitor does not appear to function properly and requires maintenance. - Regular unleaded tank probe not communicating with the ATG. |
NOV Number:
E0020210048
(Referred to Legal)
Issue Date:
1/7/2021
Expiration Date:
3/8/2021
View NOV Form
Tanks |
Violation |
3, 4 |
Failed to Empty the Tank to 1" or Less - Tanks have remained in a noncompliant red tag status for over 90 days. |
3, 4 |
Submit Notification Form For Tank Status Change - Tanks must be taken out of service. |
NOV Number:
E0020212505
(Referred to Legal)
Issue Date:
9/17/2021
Expiration Date:
11/16/2021
View NOV Form
Tanks |
Violation |
3, 4 |
Remove tank(s) - Doubled-Walled, Over 30 Years Old and OOS Over One Year - Double wall tanks that have been out of service over one year, are 30 years old and have exceeded manufacturers warranty must be removed. |
NOV Number:
E0020242595
(Pending)
Issue Date:
9/18/2024
Expiration Date:
11/17/2024
View NOV Form
Tanks |
Violation |
3, 4 |
Perform a site assessment - Tanks 3 & 4 were removed on 6/11/24. Tank removals require a site assessment pursuant to 41 Il. Adm. Code 176.330. The site assessment must be conducted or prepared under the supervision of a Licensed Professional Engineer or Professional Geologist. Within 45 days after receipt of lab results from a full site assessment the Site Assessment Results form and analytical data must be submitted to the OSFM. The electronic form can be found at our website (https://webapps.sfm.illinois.gov/USTPortal/Forms/SiteAssessmentResults). |