Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 4024603
Status: Active
Facility Name: City of Decatur Municipal Service Center Garage
Address: 2600 North Jasper Street
Decatur, IL 62526
County: Macon
Property Parcel:
Facility Type: City / Town
Owner Type: Municipal
Green Tag Decal: X001221
Green Tag Issue Date: 3/4/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: City of Decatur
Owner Address: #1 Gary K Anderson Plaza
Decatur, IL 625231196
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 10/4/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 3/4/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0021736 City of Decatur Current Owner
U0003014 City of Decatur Former Owner 10/9/1987

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

No Deficiencies Found

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/6/1989 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 10/29/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/17/2023 10/17/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/17/2023 10/17/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 10/17/2023 10/17/2024
Overfill Prev Device Overfill Alarm 6/6/2022 6/6/2025
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/6/2022 6/6/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/6/1989 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 10/29/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/17/2023 10/17/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/17/2023 10/17/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 10/17/2023 10/17/2024
Overfill Prev Device Overfill Alarm 6/6/2022 6/6/2025
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/6/2022 6/6/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/6/1989 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 10/29/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/17/2023 10/17/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/17/2023 10/17/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 10/17/2023 10/17/2024
Overfill Prev Device Overfill Alarm 6/6/2022 6/6/2025
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/6/2022 6/6/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/6/1989 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 10/29/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/17/2023 10/17/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/17/2023 10/17/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 10/17/2023 10/17/2024
Overfill Prev Device Overfill Alarm 6/6/2022 6/6/2025
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/6/2022 6/6/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 2000 Petroleum Use:
Product: New Oil CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/6/1989 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 10/29/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 10/17/2023 10/17/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 10/17/2023 10/17/2024
Overfill Prev Device Overfill Alarm 6/6/2022 6/6/2025
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/6/2022 6/6/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 1000 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 1/6/1989 Abandoned Material:
Current Age: 36 Abandoned Date:
Install Date: 10/29/1987 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Gravity Feed N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Gravity Feed N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 10/17/2023 10/17/2024
Overfill Prev Device Overfill Alarm 6/6/2022 6/6/2025
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/6/2022 6/6/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found