11 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Premium STP sump lid is missing gasket/seal, repair/replace. |
12 |
Dispensers - the following hoses or breakaways are missing or actively leaking and require immediate replacement (bagged at inspection) |
11 |
Line interstitial sensors have been raised and rendered inoperational. - Premium STP sump sensor raised. |
10, 11, 12 |
Tank monitor does not appear to function properly and requires maintenance. - ATG failed annual certification, positive shutdown not verified. |