Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 4019118
Status: Active
Facility Name: AMC Foodmart, LLC
Address: 400 East Jourdan Street
Newton, IL 62448
County: Jasper
Property Parcel: 90-12-01-228-006
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002542
Green Tag Issue Date: 11/9/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Vishat Realty, Inc.
Owner Address: 400 E. Jourdan Street
Newton, IL 62448
Owner Status: Current Owner
Purchase Date: 11/2/2020
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 1/30/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 11/9/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040460 Vishat Realty, Inc. Current Owner 11/2/2020
U0034850 Newton Petroleum, Inc. Former Owner 6/26/2008
U0011586 Parrish Oil Production, Inc. Former Owner 6/1/1986

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240907 (Pending)    Issue Date: 3/27/2024    Expiration Date: 5/26/2024    View NOV Form

Tanks Deficiency
4 Dispensers - hoses cracked, split or worn and require replacement
Facility Financial responsibility must be reported yearly - Financial Responsibility must be declared annually. The form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
6 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
4, 5, 6 Tank monitor does not appear to function properly and requires maintenance. - Tank monitor indicates a " Tank annual compliance alarm".

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
98-1442 6/15/1998 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
98-1442 Eligible 11/4/1998 12/28/1998 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 1000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 6/19/1998
OSFM First Notify Date: 3/31/1986 Abandoned Material:
Current Age: 15 Abandoned Date:
Install Date: 4/1/1983 Red Tag Issue Date:
Last Used Date: 6/17/1998 Fee Due: $0.00
Product Date: 4/1/1983

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 1000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 6/19/1998
OSFM First Notify Date: 3/31/1986 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 4/1/1986 Red Tag Issue Date:
Last Used Date: 6/17/1998 Fee Due: $0.00
Product Date: 4/1/1986

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 2000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 6/19/1998
OSFM First Notify Date: 3/31/1986 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 1/4/1974 Red Tag Issue Date:
Last Used Date: 6/17/1998 Fee Due: $0.00
Product Date: 1/5/1974

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/30/1988 Abandoned Material:
Current Age: 38 Abandoned Date:
Install Date: 4/5/1986 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/5/1986

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/30/2021 6/30/2024
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 6/30/2021 6/30/2024
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 11/10/2023 11/10/2024
Leak Detect - Tank Automatic Tank Gauging Franklin Fueling Systems EVO 200 11/10/2023 11/10/2024
Overfill Prev Device Overfill Drop Tube Valve 12/16/2021 12/16/2024
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/13/2021 12/13/2024
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test Pass 11/4/2022
Piping Flexible Double Wall Environ Geo Flex Precision Test Pass 11/10/2023



Tank Number 5

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/30/1988 Abandoned Material:
Current Age: 38 Abandoned Date:
Install Date: 4/5/1986 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/5/1986

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/30/2021 6/30/2024
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 6/30/2021 6/30/2024
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 11/10/2023 11/10/2024
Leak Detect - Tank Automatic Tank Gauging Franklin Fueling Systems EVO 200 11/10/2023 11/10/2024
Overfill Prev Device Overfill Drop Tube Valve 12/16/2021 12/16/2024
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/13/2021 12/13/2024
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test Pass 11/4/2022
Piping Flexible Double Wall Environ Geo Flex Precision Test Pass 11/10/2023



Tank Number 6

Capacity: 15000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/28/1998 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 6/8/1998 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/9/1998

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 6/30/2021 6/30/2024
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 11/10/2023 11/10/2024
Leak Detect - Tank Automatic Tank Gauging Franklin Fueling Systems EVO 200 11/10/2023 11/10/2024
Overfill Prev Device Overfill Alarm 12/14/2021 12/14/2024
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/13/2021 12/13/2024
Tank Fiberglass Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test Pass 11/4/2022
Piping Flexible Double Wall Environ Geo Flex Precision Test Pass 11/10/2023
Tank Fiberglass Single Wall Precision Test (Tank) Pass 12/17/2021



Tank Number 7

Capacity: 1000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 3/31/1986
OSFM First Notify Date: 8/28/1998 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 8

Capacity: 1000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 3/31/1986
OSFM First Notify Date: 8/28/1998 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 9

Capacity: 2000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 3/31/1986
OSFM First Notify Date: 8/28/1998 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 10

Capacity: 1000 Petroleum Use:
Product: CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 3/31/1986
OSFM First Notify Date: 8/28/1998 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 11

Capacity: 2000 Petroleum Use:
Product: CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 3/31/1986
OSFM First Notify Date: 8/28/1998 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 8S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms