Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 4008084
Status: Active
Facility Name: Casey's General Stores #2670
Address: 201 North Haughton Highway
Greenup, IL 62428
County: Cumberland
Property Parcel: 13-01-301-001
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002646
Green Tag Issue Date: 4/28/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Casey's Retail Company
Owner Address: 3305 SE Delaware Ave.
P.O. Box 3004
Ankeny, IA 50021
Owner Status: Current Owner
Purchase Date: 6/25/2007
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 10/27/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/28/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0002560 Casey's Retail Company Current Owner 6/25/2007
U0023515 Johnson Oil Company, L.L.C. Former Owner 8/3/1998
U0008722 L. Keller Oil Properties, Inc. Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241334 (Pending)    Issue Date: 5/13/2024    Expiration Date: 7/12/2024    View NOV Form

Tanks Deficiency
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

NOV Number: E0020241335 (Pending)    Issue Date: 5/13/2024    Expiration Date: 7/12/2024    View NOV Form

Tanks Deficiency
Facility Facility Operation and Maintenance Plan not updated to new requirements.
4, 5 Line leak detection equipment in alarm or failed test, must repair or replace. - Water in both STP sumps.
4, 5 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
4 Tank interstitial sensors in alarm or failed test, must repair or replace.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/20/1999
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 8/3/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/20/1999
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 8/3/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/20/1999
OSFM First Notify Date: 4/28/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 8/3/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/9/2008 Abandoned Material:
Current Age: 15 Abandoned Date:
Install Date: 5/23/2008 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/1/2008

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/5/2024 2/5/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 2/5/2024 2/5/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/5/2024 2/5/2025
Overfill Prev Device Overfill Drop Tube Valve 2/13/2023 2/13/2026
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 2/13/2023 2/13/2026
Leak Detect - Piping Sump Sensor 2/5/2024 2/5/2025
Spill Contain Device Single Wall Spill Bucket 2/13/2023 2/13/2026
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/9/2008 Abandoned Material:
Current Age: 15 Abandoned Date:
Install Date: 5/23/2008 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/1/2008

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/5/2024 2/5/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 2/5/2024 2/5/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/5/2024 2/5/2025
Overfill Prev Device Overfill Drop Tube Valve 2/13/2023 2/13/2026
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 2/13/2023 2/13/2026
Leak Detect - Piping Sump Sensor 2/5/2024 2/5/2025
Spill Contain Device Single Wall Spill Bucket 2/13/2023 2/13/2026
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 8000 Petroleum Use:
Product: B-20 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/9/2008 Abandoned Material:
Current Age: 15 Abandoned Date:
Install Date: 5/23/2008 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/1/2008

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/5/2024 2/5/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 2/5/2024 2/5/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 2/5/2024 2/5/2025
Overfill Prev Device Overfill Drop Tube Valve 2/13/2023 2/13/2026
Piping Flexible Double Wall A.P.T. Poly Tech N/A N/A
Piping Single Wall STP/Tanktop Sump 2/13/2023 2/13/2026
Leak Detect - Piping Sump Sensor 2/5/2024 2/5/2025
Spill Contain Device Single Wall Spill Bucket 2/13/2023 2/13/2026
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/13/2023 2/13/2026
Leak Detect - Piping Sump Sensor 2/5/2024 2/5/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/13/2023 2/13/2026
Leak Detect - Piping Sump Sensor 2/5/2024 2/5/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/13/2023 2/13/2026
Leak Detect - Piping Sump Sensor 2/5/2024 2/5/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/13/2023 2/13/2026
Leak Detect - Piping Sump Sensor 2/5/2024 2/5/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/13/2023 2/13/2026
Leak Detect - Piping Sump Sensor 2/5/2024 2/5/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/13/2023 2/13/2026
Leak Detect - Piping Sump Sensor 2/5/2024 2/5/2025

MFD Motorfuel Dispensing Forms