Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 3045558
Status: Active
Facility Name: Hy-Vee Gas
Address: 5421 W. War Memorial Drive
Peoria, IL 61615
County: Peoria
Property Parcel: 13-11-151-024
Facility Type: Attended Self-Service/Unattended Self-Service
Owner Type: Private
Green Tag Decal: X002287
Green Tag Issue Date: 10/11/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Hy-Vee, Inc.
Owner Address: 5820 Westown Parkway
West Des Moines, IA 50266
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Letter of Credit
Financial Responsibility Reporting Due Date: 10/23/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 10/11/2022 12/31/2024
Unattended Self Service 10/11/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0030721 Hy-Vee, Inc. Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240755 (Pending)    Issue Date: 3/13/2024    Expiration Date: 5/12/2024    View NOV Form

Tanks Deficiency
3 Line interstitial sensors have been raised and rendered inoperational. - Sensor is not on the bottom of the sump. It is rested on a tank rib and needs to be located at the bottom of the sump.
Facility Miscellaneous - STP sump lids for Tanks 2, 3 and 4 are damaged and difficlut to open. Repalce lids and repair with ones that have handles and steel rings in round. Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps a) All containment sumps must consist of a factory manufactured containment that is liquid-tight on its sides, bottom and at any penetrations and is compatible with the substance conveyed by the piping. Such containment shall also have a factory manufactured protective cover and supporting components that are properly maintained. If the protective cover or its supporting components are cracked, deteriorated or missing, the cover and supporting components that are defective shall be replaced.
1, 2, 3, 4 Miscellaneous - Midgrade at 5/6 and 15/16 have debris or liquid present. 5/6 appears tp be leaking. Clean and access dispenser 5/6.
Facility Missing copies of 30 day Walkthrough Inspection Report.
1, 2, 3, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2, 3, 4 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - All UDCs and STPs are past due

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 20000 Gasoline - Mid-grade Currently in use Federal $0.00
2 8000 Gasoline - Regular Currently in use Federal $0.00
3 6000 Gasoline - Premium Currently in use Federal $0.00
4 6000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active
13/14 Active
15/16 Active

MFD Motorfuel Dispensing Forms

No Forms Found