Deficiencies (Current)
NOV Number:
E0020240503
(Pending)
Issue Date:
2/22/2024
Expiration Date:
4/22/2024
View NOV Form
Tanks |
Deficiency |
1, 2, 3 |
Line interstitial sensors have been raised and rendered inoperational. - All UDC and Tanks 1 and 2 STP have rasied sensors. All containments also have water in them |
2 |
Miscellaneous - Check gasket in drop tube. It appears to be out of place and may be allowing water from the spill bucket into the tank. |
1, 2, 3 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |