1, 2, 3, 4, 5 |
Dispensers - hoses cracked, split or worn and require replacement |
1, 2, 3, 4, 5 |
Install corrosion protection under dispensers to protect exposed flex connectors and other metal portions of product piping. - Dispensers 3/4,5/6,& 9/10 |
1, 2, 3, 4, 5 |
Precision tank test required. - Maintain one PASSING report per TANK 1, 2,3,4,&5 per month, from ATG. Missing passing monthly reports for 10 of the last 12 months. |
1, 2, 3, 4 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
1, 2, 3, 4, 5 |
Tank monitor does not appear to function properly and requires maintenance. - Green, yellow and red light bulbs are not working. |