Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 3027019
Status: Active
Facility Name: BG Mini Mart, Inc. Shell Station #1185
Address: 502 1st Avenue
P.O. Box 74
Colona, IL 61241
County: Henry
Property Parcel: 06-10-203-025
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000371
Green Tag Issue Date: 4/10/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: BG Mini Mart, Inc.
Owner Address: 502 1st Avenue
Colona, IL 61241
Owner Status: Current Owner
Purchase Date: 8/28/2008
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 4/4/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/10/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035167 BG Mini Mart, Inc. Current Owner 8/28/2008
U0002119 B Petro Corporation f/k/a Bulk Petroleum Corporation Former Owner 8/28/2000
U0017007 Kvk Spindler Corp Former Owner 12/1/1990

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020230900 (Pending)    Issue Date: 4/11/2023    Expiration Date: 6/10/2023    View NOV Form

Tanks Deficiency
4, 6, 7 Failed to Empty the Tank to 1" or Less - Tank(s) is/are currently not in service and shall be pumped down to one inch or less of product. Due to a Tornade All Tanks have no Leak Detection due to power loss, all product must be removed

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
93-0708 3/24/1993 Removal Log
930708 3/24/1993 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
93-0708 Eligible 6/24/1997 7/21/1997 $15,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/24/1993
OSFM First Notify Date: 4/12/1991 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 1/1/1967 Red Tag Issue Date:
Last Used Date: 8/1/1991 Fee Due: $0.00
Product Date: 1/1/1967

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/24/1993
OSFM First Notify Date: 4/12/1991 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 1/1/1967 Red Tag Issue Date:
Last Used Date: 8/1/1991 Fee Due: $0.00
Product Date: 1/1/1967

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/24/1993
OSFM First Notify Date: 4/12/1991 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 1/1/1967 Red Tag Issue Date:
Last Used Date: 8/1/1991 Fee Due: $0.00
Product Date: 1/1/1967

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 8200 Petroleum Use:
Product: Gasoline - Mid-grade CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/10/1992 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 5/5/1991 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/5/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 6/30/2022 6/30/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2024 4/8/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 4/5/2024 4/5/2025
Overfill Prev Device Overfill Alarm 4/5/2024 4/5/2027
Piping Flexible Double Wall A.P.T. Poly Tech P150SC N/A N/A
Piping Single Wall STP/Tanktop Sump 11/21/2023 11/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/5/2024 4/5/2025
Spill Contain Device Double Wall Spill Bucket 11/21/2023 11/21/2026
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test Pass 4/27/2022
Piping Flexible Double Wall A.P.T. Poly Tech P150SC Precision Test Pass 4/8/2024
Piping Steel Single Wall Piping Precision Test Pass 4/27/2022
Tank STIP3 Single Wall Precision Test (Tank) Pass 4/8/2024



Tank Number 5

Capacity: 8200 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/10/1992 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 5/5/1991 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/5/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 6/30/2022 6/30/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2024 4/8/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 4/5/2024 4/5/2025
Overfill Prev Device Overfill Alarm 4/5/2024 4/5/2027
Piping Flexible Double Wall A.P.T. Poly Tech P150SC N/A N/A
Piping Single Wall STP/Tanktop Sump 11/21/2023 11/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/5/2024 4/5/2025
Spill Contain Device Double Wall Spill Bucket 11/21/2023 11/21/2026
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test Pass 4/27/2022
Piping Flexible Double Wall A.P.T. Poly Tech P150SC Precision Test Pass 4/8/2024
Piping Steel Single Wall Piping Precision Test Pass 4/27/2022
Tank STIP3 Single Wall Precision Test (Tank) Pass 4/8/2024



Tank Number 6

Capacity: 4000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/10/1992 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 5/5/1991 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/5/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 6/30/2022 6/30/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2024 4/8/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 4/5/2024 4/5/2025
Overfill Prev Device Overfill Alarm 4/5/2024 4/5/2027
Piping Flexible Double Wall A.P.T. Poly Tech P150SC N/A N/A
Piping Single Wall STP/Tanktop Sump 11/21/2023 11/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/5/2024 4/5/2025
Spill Contain Device Double Wall Spill Bucket 11/21/2023 11/21/2026
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test Pass 4/27/2022
Piping Flexible Double Wall A.P.T. Poly Tech P150SC Precision Test Pass 4/8/2024
Piping Steel Single Wall Piping Precision Test Pass 4/27/2022
Tank STIP3 Single Wall Precision Test (Tank) Pass 4/8/2024



Tank Number 7

Capacity: 4000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/7/1992 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 5/5/1991 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/5/1991

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 6/30/2022 6/30/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2024 4/8/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 4/5/2024 4/5/2025
Overfill Prev Device Overfill Alarm 4/5/2024 4/5/2027
Piping Flexible Double Wall A.P.T. Poly Tech P150SC N/A N/A
Piping Single Wall STP/Tanktop Sump 11/21/2023 11/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/5/2024 4/5/2025
Spill Contain Device Double Wall Spill Bucket 11/21/2023 11/21/2026
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech Precision Test Pass 4/27/2022
Piping Flexible Double Wall A.P.T. Poly Tech P150SC Precision Test Pass 4/8/2024
Piping Steel Single Wall Piping Precision Test Pass 4/27/2022
Tank STIP3 Single Wall Precision Test (Tank) Pass 4/8/2024



Tank Number 8

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 3/24/1993
OSFM First Notify Date: 3/29/1993 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1967 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 9

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 3/24/1993
OSFM First Notify Date: 3/29/1993 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1967 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 10

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 3/24/1993
OSFM First Notify Date: 3/29/1993 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/31/1967 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/21/2023 11/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/5/2024 4/5/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/21/2023 11/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/5/2024 4/5/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/21/2023 11/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/5/2024 4/5/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/21/2023 11/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/5/2024 4/5/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/21/2023 11/21/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/5/2024 4/5/2025

MFD Motorfuel Dispensing Forms

No Forms Found