Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 3025522
Status: Inactive
Facility Name: Detweiller Marina
Address: Foot of Caroline Street
Peoria, IL 61603
County: Peoria
Property Parcel: 18-03-426-001
Facility Type: Marina
Owner Type: Private
Green Tag Decal: Extend
Green Tag Issue Date: 12/28/2020
Green Tag Expiration Date: 2/9/2021

Owner Details

Owner Name: Detweiller Playground, Inc.
Owner Address: 301 SW Adams Street
1st of America Bank
Peoria, IL 61631
Owner Status: Current Owner
Purchase Date: 5/17/1990
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/29/2019

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Marina 6/18/2018 12/31/2020

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0004043 Detweiller Playground, Inc. Current Owner 5/17/1990

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020203233 (Referred to Legal)    Issue Date: 11/10/2020    Expiration Date: 1/9/2021    View NOV Form

Tanks Deficiency
Facility A/B operator retraining required as a result of issuance of the Notice of Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
3 Annual leak detection certification not completed (Required annually). - All automatic tank gauge components must be tested.
3 Annual line precision and mechanical line leak detector functional test not completed.
Facility Emergency contact information for A/B & C Operators not posted at unmanned facility
Facility Facility Operation and Maintenance Plan not completed or available.
Facility Financial responsibility must be reported yearly
3 Line interstitial sensor functional test not accomplished (Required annually).
3 Miscellaneous - The product piping must have breakaway devices installed on shore where the piping approaches the dock or other floating structure (refer to section 175.460(b)(2).
Facility Missing copies of 30 day Walkthrough Inspection Report.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training
Facility Missing copy of emergency instructions or emergency procedures plan
Facility Missing list of designated Class A/B & C Operators
3 Monthly line interstitial sensor records not available.
3 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
3 Required monthly tank interstitial sensor records not available.
3 Required monthly tank leak test records not available.
3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
3 Triennial spill prevention equipment testing not completed.
3 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Every sump that contains an interstitial piping sump sensor must be tested every 3 years (the submersible pump sump, the dispenser sump, the shore line piping shut-off sump, and the transition sump).

NOV Number: E0020213111 (Referred to Legal)    Issue Date: 11/23/2021    Expiration Date: 1/22/2022    View NOV Form

Tanks Deficiency
3 Remove tank(s) - Doubled-Walled, Over 30 Years Old and OOS Over One Year

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 8000 Gasoline Removed Federal $0.00 05/17/1990 - REM
2 1000 Diesel Fuel Removed Federal $0.00 05/17/1990 - REM
3 6000 Gasoline - Regular Condemned Tank Federal 2/9/2021 $0.00

Dispenser Information

Name\ID Status
1/2 Active

MFD Motorfuel Dispensing Forms

No Forms Found