Deficiencies (Current)
NOV Number:
E0020240845
(Pending)
Issue Date:
3/20/2024
Expiration Date:
5/19/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Fire Extinguishers - 2 4A:60BC extinguishers not provided, 1 at or near control station and 1 in the dispensing areas - Missing Fire Extinguisher 1 4A:60BC at fuel island. |
Facility |
Miscellaneous |
NOV Number:
E0020240846
(Pending)
Issue Date:
3/20/2024
Expiration Date:
5/19/2024
View NOV Form
Tanks |
Deficiency |
1, 2, 3 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Containment support components are deteriorated or missing for all STP's. Replace containment support components for tank 1,2,3 STP's. |
Facility |
Miscellaneous - Repair flex connector sacrificial anode and retest.
Sacrificial anode wire broken for Disp. 3/4 RUL & 5/6 midgrade. |
2, 3 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). |
2, 3 |
Triennial spill prevention equipment testing not completed. |