Deficiencies (Current)
NOV Number:
E0020240534
(Pending)
Issue Date:
2/27/2024
Expiration Date:
4/27/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Miscellaneous - DSL filter under dispenser 3/4 is dripping fluid. Repair or replace. |
Facility |
Miscellaneous - Tank 2 ball float valve appears to have been removed and an overfill flapper valve installed without a permit. Per 41 IAC 175.300(k), a permit for both activities shall be pulled by a third party. |
Facility |
Missing list of designated Class A/B & C Operators - Left blank onsite |
1, 2 |
Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - Dispenser 1/2 has water in the UDC. |
NOV Number:
E0020240536
(Pending)
Issue Date:
2/27/2024
Expiration Date:
4/27/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. |