Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 3018453
Status: Active
Facility Name: Hometown Express #5
Address: 106 S. Chicago St.
Geneseo, IL 612542104
County: Henry
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X000225
Green Tag Issue Date: 3/11/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: HTE, Inc.
Owner Address: 106 S. Chicago Street
Geneseo, IL 61254
Owner Status: Current Owner
Purchase Date: 10/1/2015
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 1/9/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/11/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036108 HTE, Inc. Current Owner 10/1/2015
U0035116 River Valley Co-op Former Owner
U0003417 Cooperative Gas & Oil Company Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241037 (Pending)    Issue Date: 4/9/2024    Expiration Date: 6/8/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
4, 5, 6, 7 Annual leak detection certification not completed (Required annually).
4, 5, 6, 7 Annual line precision and mechanical line leak detector functional test not completed.
6, 7 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Repair or replace ground cover to allow for inspection
5, 6, 7 Dispensers - hoses cracked, split or worn and require replacement
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copy of emergency instructions or emergency procedures plan - This form can be found at https://sfm.illinois.gov/about/divisions/petroleum-chemical-safety/applications-and-forms.html
Facility Operations & Maintenance plan missing required frequencies
4, 5, 6, 7 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
4, 5, 6, 7 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
4, 5 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
4 Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - Dispenser 7/8 Satellite
4 Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - STP containment

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
97-1627 9/2/1997 Removal Log

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 6000 Gasoline Removed Federal $0.00 09/02/1997 - REM
2 8000 Gasoline Removed Federal $0.00 09/02/1997 - REM
3 15000 Diesel Fuel Removed Federal $0.00 09/02/1997 - REM
4 12000 Diesel Fuel Currently in use Federal $0.00
5 12000 Gasoline - Regular Currently in use Federal $0.00
6 6000 Gasoline - Mid-grade Currently in use Federal $0.00
7 5000 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
8S Active

MFD Motorfuel Dispensing Forms

No Forms Found