Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 3011717
Status: Active
Facility Name: Third Street Mart, Inc. - CK United #4701248
Address: 237 West 3rd Street
Dallas City, IL 62330
County: Hancock
Property Parcel: 04-02-000-434
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001641
Green Tag Issue Date: 1/30/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: CK United, LLC
Owner Address: 300 N. Martingale Rd.
Suite 750
Schaumburg, IL 60173
Owner Status: Current Owner
Purchase Date: 12/13/2021
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/31/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/30/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040495 CK United, LLC Current Owner 12/13/2021
U0030949 Mac's Convenience Stores, LLC Former Owner 4/18/2005
U0031578 J & D Meyer Ltd. Former Owner 8/15/2003
U0002262 Wareco Service, Inc. Former Owner 3/7/2001
U0006028 Gracey Iii Had Former Owner 12/31/1967
U0029789 Clark Retail Enterprises, Inc. Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

No Deficiencies Found

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/13/1999
OSFM First Notify Date: 5/4/1986 Abandoned Material:
Current Age: 14 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/22/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 5000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/13/1999
OSFM First Notify Date: 5/4/1986 Abandoned Material:
Current Age: 14 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/22/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 1000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 1/1/1986
OSFM First Notify Date: 5/4/1986 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 500 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 1/1/1986
OSFM First Notify Date: 5/4/1986 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 560 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 7/13/1999
OSFM First Notify Date: 11/9/1986 Abandoned Material:
Current Age: 13 Abandoned Date:
Install Date: 1/1/1986 Red Tag Issue Date:
Last Used Date: 12/22/1998 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/3/1999 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 12/11/1998 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/11/1998

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 11/17/2023 11/17/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 11/17/2023 11/17/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 11/17/2023 11/17/2024
Overfill Prev Device Overfill Drop Tube Valve 8/22/2022 8/22/2025
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive
Piping Single Wall STP/Tanktop Sump 8/22/2022 8/22/2025
Leak Detect - Piping Sump Sensor 11/17/2023 11/17/2024
Spill Contain Device Double Wall Spill Bucket 8/22/2022 8/22/2025
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Precision Test Pass 11/17/2023
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors Sensor Functional Pass 2/25/2010
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 2/25/2010



Tank Number 7

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 2/3/1999 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 12/11/1998 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 12/11/1998

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 11/17/2023 11/17/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 11/17/2023 11/17/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 11/17/2023 11/17/2024
Overfill Prev Device Overfill Drop Tube Valve 8/22/2022 8/22/2025
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive
Piping Single Wall STP/Tanktop Sump 8/22/2022 8/22/2025
Leak Detect - Piping Sump Sensor 11/17/2023 11/17/2024
Spill Contain Device Double Wall Spill Bucket 8/22/2022 8/22/2025
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Enviroflex non-corrosive Precision Test Pass 11/17/2023
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors Sensor Functional Pass 2/25/2010
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 2/25/2010

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found