Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 3007525
Status: Active
Facility Name: Krishu Convenience Store
Address: 1901 16th Street
Moline, IL 61265
County: Rock Island
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X000261
Green Tag Issue Date: 7/18/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Sirumaya, LLC
Owner Address: 1901 16th Street
Moline, IL 61265
Owner Status: Current Owner
Purchase Date: 9/19/2016
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/12/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/16/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038485 Sirumaya, LLC Current Owner 9/19/2016
U0036637 Basnet Incorporated Former Owner 8/17/2012
U0034989 Pal Petro, Inc. Former Owner 6/1/2007
U0031999 Convenience & Petroleum Marketing, LLC, Former Owner 8/8/2006
U0008697 Kwik Shop, Inc. Former Owner 10/17/1988
U0022393 The Southland Corporation Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240912 (Pending)    Issue Date: 3/27/2024    Expiration Date: 5/26/2024    View NOV Form

Tanks Deficiency
1 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - All tank ground covers for STP sumps are deteriorated and need replaced.
1 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - RUL ATG ground cover damaged and needs replacement
2 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - All tank ground covers for STP sumps are deteriorated and need replaced.
2 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Mid Grade ATG containment deteriorated needs replacement.
3 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - All tank ground covers for STP sumps are deteriorated and need replaced.
Facility Facility Operation and Maintenance Plan not completed or available.
Facility Missing copy of emergency instructions or emergency procedures plan
Facility Missing list of designated Class A/B & C Operators
3 Open electrical conduit or junction boxes. - PUL open junction box in STP sump
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Mid-grade Currently in use Federal $0.00
3 6000 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active

MFD Motorfuel Dispensing Forms