Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2047442
Status: Active
Facility Name: Casey's General Stores #3981
Address: 2601 East Lincoln Highway
New Lenox, IL 60451
County: Will
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X000310
Green Tag Issue Date: 11/10/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Casey's Retail Company
Owner Address: 3305 SE Delaware Ave.
P.O. Box 3004
Ankeny, IA 50021
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 10/27/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 11/10/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0002560 Casey's Retail Company Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240750 (Pending)    Issue Date: 3/13/2024    Expiration Date: 5/12/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
Facility Missing copies of current testing certificates for operator training - Missing entire compliance binder.
Facility Missing copy of written UST facility operation & maintenance plan - Missing entire compliance binder.
Facility Missing list of designated Class A/B & C Operators - Missing entire compliance binder.
1, 2, 3, 4, 5 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
5 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Ingress of water in STP sump approximately every 2 days. Repair sump to stop ingress of water.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 22000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/31/2022 Abandoned Material:
Current Age: 1 Abandoned Date:
Install Date: 6/30/2022 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/27/2022

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/28/2023 11/28/2024
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/28/2023 11/28/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 11/28/2023 11/28/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 11/28/2023 11/28/2024
Overfill Prev Device Overfill Drop Tube Valve 11/3/2022 11/3/2025
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 8/25/2022 8/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 11/28/2023 11/28/2024
Piping Single Wall STP/Tanktop Sump 8/25/2022 8/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 11/28/2023 11/28/2024
Spill Contain Device Single Wall Spill Bucket 8/25/2022 8/25/2025
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test Pass 11/3/2022
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 11/3/2022



Tank Number 2

Capacity: 14000 Petroleum Use:
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/31/2022 Abandoned Material:
Current Age: 1 Abandoned Date:
Install Date: 6/30/2022 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/27/2022

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/28/2023 11/28/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 11/28/2023 11/28/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 11/28/2023 11/28/2024
Overfill Prev Device Overfill Drop Tube Valve 11/3/2022 11/3/2025
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 8/25/2022 8/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 11/28/2023 11/28/2024
Spill Contain Device Single Wall Spill Bucket 8/25/2022 8/25/2025
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test Pass 11/3/2022
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 11/3/2022



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/31/2022 Abandoned Material:
Current Age: 1 Abandoned Date:
Install Date: 6/23/2022 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/27/2022

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/28/2023 11/28/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 11/28/2023 11/28/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 11/28/2023 11/28/2024
Overfill Prev Device Overfill Drop Tube Valve 11/3/2022 11/3/2025
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 8/25/2022 8/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 11/28/2023 11/28/2024
Spill Contain Device Single Wall Spill Bucket 8/25/2022 8/25/2025
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test Pass 11/3/2022
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 11/3/2022



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/31/2022 Abandoned Material:
Current Age: 1 Abandoned Date:
Install Date: 6/30/2022 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/27/2022

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/28/2023 11/28/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 11/28/2023 11/28/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 11/28/2023 11/28/2024
Overfill Prev Device Overfill Drop Tube Valve 11/3/2022 11/3/2025
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 8/25/2022 8/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 11/28/2023 11/28/2024
Spill Contain Device Single Wall Spill Bucket 8/25/2022 8/25/2025
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test Pass 11/3/2022
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 11/3/2022



Tank Number 5

Capacity: 8000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/31/2022 Abandoned Material:
Current Age: 1 Abandoned Date:
Install Date: 6/30/2022 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/27/2022

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/28/2023 11/28/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 11/28/2023 11/28/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 11/28/2023 11/28/2024
Overfill Prev Device Overfill Drop Tube Valve 11/3/2022 11/3/2025
Piping Flexible Double Wall A.P.T. Poly Tech P175SC N/A N/A
Piping Single Wall STP/Tanktop Sump 4/5/2024 4/5/2027
Leak Detect - Piping Sump Sensor with positive shutdown 11/28/2023 11/28/2024
Spill Contain Device Single Wall Spill Bucket 8/25/2022 8/25/2025
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall A.P.T. Poly Tech P175SC Precision Test Pass 11/3/2022
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 11/3/2022

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/25/2022 8/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 11/28/2023 11/28/2024



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/25/2022 8/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 11/28/2023 11/28/2024



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/25/2022 8/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 11/28/2023 11/28/2024



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/25/2022 8/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 11/28/2023 11/28/2024



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/25/2022 8/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 11/28/2023 11/28/2024



Name\ID 19/20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/25/2022 8/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 11/28/2023 11/28/2024



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/25/2022 8/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 11/28/2023 11/28/2024



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/25/2022 8/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 11/28/2023 11/28/2024



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/25/2022 8/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 11/28/2023 11/28/2024



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 8/25/2022 8/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 11/28/2023 11/28/2024

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2047442 Casey's General Stores #3981 New Lenox 11/04/2022 Letter Form