Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2047034
Status: Active
Facility Name: 7-Eleven Store #38672
Address: 244 Washington St.
Oswego, IL 60543
County: Kendall
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X000757
Green Tag Issue Date: 3/14/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: GW Oswego LLC
Owner Address: 2211 N Elston Ave.
Chicago, IL 60614
Owner Status: Current Owner
Purchase Date: 3/18/2019
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/13/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/14/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039819 GW Oswego LLC Current Owner 3/18/2019

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241134 (Pending)    Issue Date: 4/17/2024    Expiration Date: 6/16/2024    View NOV Form

Tanks Deficiency
1, 2, 3 Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/8/2020 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 5/1/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/5/2023 7/5/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 7/17/2023 7/17/2024
Overfill Prev Device Overfill Drop Tube Valve 7/5/2023 7/5/2026
Piping Flexible Double Wall OPW Flexworks N/A N/A
Piping Single Wall STP/Tanktop Sump 3/10/2023 3/10/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/5/2023 7/5/2024
Spill Contain Device Double Wall Spill Bucket 7/5/2023 7/5/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Flexworks Precision Test Pass 9/2/2020
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 9/2/2020



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/8/2020 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 5/1/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/5/2023 7/5/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 7/5/2023 7/5/2024
Overfill Prev Device Overfill Drop Tube Valve 7/5/2023 7/5/2026
Piping Flexible Double Wall OPW Flexworks N/A N/A
Piping Single Wall STP/Tanktop Sump 3/10/2023 3/10/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/5/2023 7/5/2024
Spill Contain Device Double Wall Spill Bucket 7/5/2023 7/5/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Flexworks Precision Test Pass 9/2/2020
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 9/2/2020



Tank Number 3

Capacity: 12000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/8/2020 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 5/1/2020 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/5/2023 7/5/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 7/5/2023 7/5/2024
Overfill Prev Device Overfill Drop Tube Valve 7/5/2023 7/5/2026
Piping Flexible Double Wall OPW Flexworks N/A N/A
Piping Single Wall STP/Tanktop Sump 3/10/2023 3/10/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/5/2023 7/5/2024
Spill Contain Device Double Wall Spill Bucket 7/5/2023 7/5/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall OPW Flexworks Precision Test Pass 9/2/2020
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 9/2/2020

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/10/2023 3/10/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/5/2023 7/5/2024



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/10/2023 3/10/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/5/2023 7/5/2024



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/10/2023 3/10/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/5/2023 7/5/2024



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/10/2023 3/10/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/5/2023 7/5/2024



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/10/2023 3/10/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/5/2023 7/5/2024



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 3/10/2023 3/10/2026
Leak Detect - Piping Sump Sensor with positive shutdown 7/5/2023 7/5/2024

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2047034 7-Eleven Store #38672 Oswego 04/08/2020 Letter Form