Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2046902
Status: Active
Facility Name: Love's Travel Stop #770
Address: 43100 US Highway 41
Wadsworth, IL 60083
County: Lake
Property Parcel: 03-04-300-054
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003761
Green Tag Issue Date: 10/4/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Love's Travel Stops & Country Stores, Inc.
Owner Address: P.O. Box 26210
10601 N. Penn
Oklahoma City, OK 73120
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/28/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 10/4/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0030965 Love's Travel Stops & Country Stores, Inc. Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241031 (Pending)    Issue Date: 4/9/2024    Expiration Date: 6/8/2024    View NOV Form

Tanks Deficiency
5 Line leak detection equipment in alarm or failed test, must repair or replace. - Sump sensor with positive shutdown failed test. Faulty sensor located in the north diesel tank interstitial.
5 Tank interstitial sensors in alarm or failed test, must repair or replace. - ATG and non discrimitating intersititial monitoring sensors failed test. Tank probes are missing.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/20/2019 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 8/16/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/4/2024 3/4/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/4/2024 3/4/2025
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Automatic Tank Gauging Incon EVO 5000 3/4/2024 3/4/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/4/2024 3/4/2025
Overfill Prev Device Overfill Alarm 3/4/2024 3/4/2027
Overfill Prev Device Overfill Drop Tube Valve 3/4/2024 3/4/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor 3/14/2023 3/14/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025
Piping Single Wall Transition Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025
Spill Contain Device Single Wall Spill Bucket 6/19/2023 6/19/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Siphon Bar Functional Pass 3/14/2023
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 5/5/2021
Piping Fiberglass Secondary Containment Ameron Precision Test Pass 6/30/2020
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 7/1/2020



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/20/2019 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 8/16/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Automatic Tank Gauging Incon EVO 5000 3/4/2024 3/4/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/4/2024 3/4/2025
Overfill Prev Device Overfill Alarm 3/4/2024 3/4/2027
Overfill Prev Device Overfill Drop Tube Valve 3/4/2024 3/4/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor 3/14/2023 3/14/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025
Piping Single Wall Transition Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025
Spill Contain Device Single Wall Spill Bucket 6/19/2023 6/19/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Siphon Bar Functional Pass 3/14/2023
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 6/30/2020
Piping Fiberglass Secondary Containment Ameron Precision Test Pass 6/30/2020
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 7/1/2020



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/20/2019 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 8/16/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/4/2024 3/4/2025
Leak Detect - Tank Automatic Tank Gauging Incon EVO 5000 3/4/2024 3/4/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/4/2024 3/4/2025
Overfill Prev Device Overfill Alarm 3/4/2024 3/4/2027
Overfill Prev Device Overfill Drop Tube Valve 3/4/2024 3/4/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor 3/14/2023 3/14/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025
Piping Single Wall Transition Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025
Spill Contain Device Single Wall Spill Bucket 6/19/2023 6/19/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 5/5/2021
Piping Fiberglass Secondary Containment Ameron Precision Test Pass 6/30/2020
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 7/1/2020



Tank Number 4

Capacity: 30000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/20/2019 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 8/16/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/4/2024 3/4/2025
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Automatic Tank Gauging Incon EVO 5000 3/4/2024 3/4/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/4/2024 3/4/2025
Overfill Prev Device Overfill Alarm 3/4/2024 3/4/2027
Overfill Prev Device Overfill Drop Tube Valve 3/4/2024 3/4/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor 3/14/2023 3/14/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025
Piping Single Wall Transition Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025
Spill Contain Device Single Wall Spill Bucket 6/19/2023 6/19/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Siphon Bar Functional Pass 3/14/2023
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 5/5/2021
Piping Fiberglass Secondary Containment Ameron Precision Test Pass 6/30/2020
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 7/1/2020



Tank Number 5

Capacity: 30000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/20/2019 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 8/16/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/4/2024 3/4/2025
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Automatic Tank Gauging Incon EVO 5000 3/14/2023 3/4/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/14/2023 3/4/2024
Overfill Prev Device Overfill Alarm 3/4/2024 3/4/2027
Overfill Prev Device Overfill Drop Tube Valve 3/4/2024 3/4/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor 3/14/2023 3/14/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025
Piping Single Wall Transition Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/14/2023 3/4/2024
Spill Contain Device Single Wall Spill Bucket 6/19/2023 6/19/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Siphon Bar Functional Pass 3/14/2023
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 10/20/2022
Piping Fiberglass Secondary Containment Ameron Precision Test Pass 6/30/2020
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 7/1/2020



Tank Number 6

Capacity: 20000 Petroleum Use: None
Product: B-99 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/20/2019 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 8/16/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/4/2024 3/4/2025
Leak Detect - Tank Automatic Tank Gauging Incon EVO 5000 3/4/2024 3/4/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/4/2024 3/4/2025
Overfill Prev Device Overfill Alarm 3/4/2024 3/4/2027
Overfill Prev Device Overfill Drop Tube Valve 3/4/2024 3/4/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor 3/14/2023 3/14/2024
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025
Spill Contain Device Single Wall Spill Bucket 6/19/2023 6/19/2026
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 3/4/2024
Piping Fiberglass Secondary Containment Ameron Precision Test Pass 6/30/2020
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 7/1/2020



Tank Number 7

Capacity: 20000 Petroleum Use: None
Product: Diesel Exhaust Fluid (Non-Regulated) CERCLA Substance:
Status: Unknown CAS Code:
Regulated Status: Non-Regulated Removed Date:
OSFM First Notify Date: 8/20/2019 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 8/16/2019 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Leak Detect - Piping Sump Sensor 5/5/2021 5/5/2022
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/5/2021 5/5/2022
Overfill Prev Device Overfill Alarm 6/30/2020 6/30/2023
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Fiberglass Secondary Containment Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 6/30/2020 6/30/2023
Spill Contain Device Field Constructed 6/30/2020 6/30/2023
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 6/30/2020
Piping Fiberglass Secondary Containment Ameron Precision Test Pass 6/30/2020
Tank Fiberglass Double Wall XERXES Precision Test (Tank) Pass 7/1/2020

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 17/18S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 17S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 18/19S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 19/20S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 20/21S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 21/22S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 22/23S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 23/24S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 24/25S

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 25

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/19/2023 6/19/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2046902 Love's Travel Stop #770 Wadsworth 07/14/2020 Letter Form