Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2045891
Status: Active
Facility Name: Murphy USA #7600
Address: 985 Central Park Drive
Crystal Lake, IL 60014
County: McHenry
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003326
Green Tag Issue Date: 7/21/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Murphy Oil USA, Inc.
Owner Address: 200 E. Peach Street
El Dorado, AR 71730
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/29/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 4/20/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0029289 Murphy Oil USA, Inc. Current Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00399-2024UPG Upgrade Approved / Issued 4/5/2024 4/9/2024 10/9/2024 Documents

Deficiencies (Current)

NOV Number: E0020240921 (Pending)    Issue Date: 3/28/2024    Expiration Date: 5/27/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain 2 years on site with other annual testing documentation.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and 2 years of documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom. NOT PROPERLY FILLED OUT.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
1, 2, 3, 4 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1, 2, 3, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
3, 4 Spill prevention equipment failed triennial testing. Must be repaired or replaced. - Triennial inspection/testing of spill bucket(s) has failed. Repair/replace as necessary; devices shall be retested with passing results.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 25000 Gasoline - Regular Currently in use Federal $0.00
2 8000 Gasoline - Premium Currently in use Federal $0.00
3 10000 Diesel Fuel Currently in use Federal $0.00
4 8000 E85 Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active

MFD Motorfuel Dispensing Forms