Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2045468
Status: Active
Facility Name: Glogovsky Oil Company V, Inc. d/b/a Lake in the Hills Shell
Address: 4231 W. Algonquin Rd.
Lake in the Hills, IL 60156
County: McHenry
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003339
Green Tag Issue Date: 8/5/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Glogovsky Oil Company V, Inc.
Owner Address: 4231 W. Algonquin Road
Lake in the Hills, IL 60156
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/29/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 8/5/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038258 Glogovsky Oil Company V, Inc. Current Owner
U0028790 Glogevsky Petroleum Company Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240655 (Pending)    Issue Date: 3/6/2024    Expiration Date: 5/5/2024    View NOV Form

Tanks Deficiency
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers.

NOV Number: E0020240656 (Pending)    Issue Date: 3/6/2024    Expiration Date: 5/5/2024    View NOV Form

Tanks Deficiency
1, 2, 3, 4 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps a) All containment sumps must consist of a factory manufactured containment that is liquid-tight on its sides, bottom and at any penetrations and is compatible with the substance conveyed by the piping. Such containment shall also have a factory manufactured protective cover and supporting components that are properly maintained. If the protective cover or its supporting components are cracked, deteriorated or missing, the cover and supporting components that are defective shall be replaced. ALL STP LIDS MISSING HANDLES.
1, 2, 3, 4 Dispensers - hoses cracked, split or worn and require replacement

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 20000 Gasoline - Regular Currently in use Federal $0.00
2 6000 Gasoline - Premium Currently in use Federal $0.00
3 10000 Diesel Fuel Currently in use Federal $0.00
4 6000 E85 Currently in use Federal $0.00

Dispenser Information

Name\ID Status
17 sat Active
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active
13/14 Active
15/16 Active
17 Active

MFD Motorfuel Dispensing Forms

No Forms Found