Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2042841
Status: Active
Facility Name: Bucky's Express #6546
Address: 6551 Route 34 (at Orchard Road)
Oswego, IL 60543
County: Kendall
Property Parcel: 02-13-326-019
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003263
Green Tag Issue Date: 12/21/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Casey's Retail Company
Owner Address: 3305 SE Delaware Ave.
P.O. Box 3004
Ankeny, IA 50021
Owner Status: Current Owner
Purchase Date: 5/18/2021
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 10/27/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 11/22/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0002560 Casey's Retail Company Current Owner 5/18/2021
U0036012 Buchanan Energy (S), LLC Former Owner 12/9/2010
U0010471 Exxon Mobil Oil Corporation Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241118 (Pending)    Issue Date: 4/16/2024    Expiration Date: 6/15/2024    View NOV Form

Tanks Deficiency
1, 2, 3, 4 Line interstitial sensors have been raised and rendered inoperational. - T1-T3 STP sump sensors are on manway. All sensors must be installed at the bottom of sumps or per manufactures specification. T4 must be checked also. I was unable to get sump opened.
2 Line leak detection equipment in alarm or failed test, must repair or replace. - ATG in alarm (Q2 Annual Line Fail). Repair must be made to clear alarm.
4 Miscellaneous - I'm unable to get Diesel STP sump open. Repair so I'm able to open sump when I retuern.
1, 2, 3, 4 Monthly line interstitial sensor records not available. - Monthly line sensor report is not being kept as required.
1, 2, 3, 4 Precision line test required.
1, 2, 3, 4 Precision tank test required.
1, 2, 3, 4 Required monthly tank interstitial sensor records not available. - Monthly tank sensors records are missing.
3 Tank interstitial sensors in alarm or failed test, must repair or replace. - ATG is in alarm (L3 High Liquid Alarm). Repair so sensor is functioning properly and alarm is cleared.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 15000 Gasoline - Regular Currently in use Federal $0.00
2 15000 Gasoline - Regular Currently in use Federal $0.00
3 12000 Gasoline - Premium Currently in use Federal $0.00
4 8000 B-11 Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active
13/14 Active
15/16 Active

MFD Motorfuel Dispensing Forms