Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2042678
Status: Active
Facility Name: Mobil Gas
Address: 5701 W. Fullerton Ave.
Chicago, IL 60639
County: Cook
Property Parcel: 13-32-205-008-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002394
Green Tag Issue Date: 10/27/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: West Fullerton Properties, Inc.
Owner Address: 5701 W. Fullerton Ave.
Chicago, IL 60639
Owner Status: Current Owner
Purchase Date: 10/29/2020
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 4/15/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 8/8/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040028 West Fullerton Properties, Inc. Current Owner 10/29/2020
U0035795 HATEEB, Inc. Former Owner 6/7/2005
U0032556 Hassan, Fayik Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241114 (Pending)    Issue Date: 4/15/2024    Expiration Date: 6/14/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2 Annual leak detection certification not completed (Required annually).
1, 2 Annual line precision and mechanical line leak detector functional test not completed.
1, 2 Line interstitial sensor functional test not accomplished (Required annually).
Facility Missing copies of Annual Walkthrough Inspection Report.
1, 2 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1, 2 Tank interstitial sensor functional test not accomplished (Required annually).
1 Tank interstitial sensors in alarm or failed test, must repair or replace. - Either sensor is malfunctuioing or interstital space is full of liquid. Need to make repair and test tank.
1 Tank precision test required. - Tank needs to be tested after repair of sump sensor and missing tapes from monthly testing.
1, 2 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Dispenser and submersible sumps.
1, 2 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Both tank top submersible sumps need repair to keep water out of containment.
1, 2 Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - Dispenser 1/2 and 5/6 need to be repaired to keep water out of the sump.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/1/2005 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 7/1/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/9/2024 5/9/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 5/9/2024 5/9/2025
Overfill Prev Device Overfill Drop Tube Valve 3/10/2022 3/10/2025
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 5/9/2024 5/9/2027
Leak Detect - Piping Sump Sensor 5/9/2024 5/9/2025
Spill Contain Device Single Wall Spill Bucket 3/10/2022 3/10/2025
Tank Composite Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test Pass 5/9/2024
Tank Composite Double Wall Precision Test (Tank) Pass 5/9/2024



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 9/1/2005 Abandoned Material:
Current Age: 18 Abandoned Date:
Install Date: 7/1/2005 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/2005

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/9/2024 5/9/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 5/9/2024 5/9/2025
Overfill Prev Device Overfill Drop Tube Valve 3/10/2022 3/10/2025
Piping Flexible Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 12/17/2020 12/17/2023
Leak Detect - Piping Sump Sensor 5/9/2024 5/9/2025
Spill Contain Device Single Wall Spill Bucket 3/10/2022 3/10/2025
Tank Composite Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Precision Test Pass 5/9/2024
Tank Composite Double Wall Precision Test (Tank) Pass 10/21/2020

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/9/2024 5/9/2027
Leak Detect - Piping Sump Sensor 5/9/2024 5/9/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/9/2024 5/9/2027
Leak Detect - Piping Sump Sensor 5/9/2024 5/9/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/9/2024 5/9/2027
Leak Detect - Piping Sump Sensor 5/9/2024 5/9/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 5/9/2024 5/9/2027
Leak Detect - Piping Sump Sensor 5/9/2024 5/9/2025

MFD Motorfuel Dispensing Forms