Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2042316
Status: Active
Facility Name: Langley Gas & Mini Mart
Address: 11101 S. Langley Avenue
Chicago, IL 60628
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X001275
Green Tag Issue Date: 3/30/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Khalid Siddiqui
Owner Address: 1823 W Hood Ave -#C
Chicago, IL 60660
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 5/11/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/30/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0025320 Siddiqui, Khalid Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241192 (Pending)    Issue Date: 4/22/2024    Expiration Date: 6/21/2024    View NOV Form

Tanks Deficiency
1, 4, 5 Line interstitial sensors have been raised and rendered inoperational. - Lower sensor in Diesel and Regular STP Sumps. Also lower sensor in dispenser 7/8 sump.
Facility Missing list of designated Class A/B & C Operators
1, 4, 5 Required monthly tank leak test records not available. - Printout CSLD/Liquid Status Report monthly.
4, 5 Tank interstitial sensors in alarm or failed test, must repair or replace. - Fuel Alarm on Premium/Diesel Tank Interstice.
1, 4, 5 Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - Remove water form Dispenser 7/8

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/12/2006 Abandoned Material:
Current Age: 17 Abandoned Date:
Install Date: 9/15/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/15/2006

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/15/2024 4/15/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 4/15/2024 4/15/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/15/2024 4/15/2025
Overfill Prev Device Overfill Drop Tube Valve 2/21/2022 2/21/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 2/21/2022 2/21/2025
Leak Detect - Piping Sump Sensor 4/15/2024 4/15/2025
Spill Contain Device Single Wall Spill Bucket 2/21/2022 2/21/2025
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test Pass 4/15/2024



Tank Number 2

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/30/2005
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 5000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/30/2005
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 6000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/12/2006 Abandoned Material:
Current Age: 17 Abandoned Date:
Install Date: 9/15/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/15/2024 4/15/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 4/15/2024 4/15/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/15/2024 4/15/2025
Overfill Prev Device Overfill Drop Tube Valve 2/21/2022 2/21/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 2/21/2022 2/21/2025
Leak Detect - Piping Sump Sensor 4/15/2024 4/15/2025
Spill Contain Device Single Wall Spill Bucket 2/21/2022 2/21/2025
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test Pass 4/15/2024



Tank Number 5

Capacity: 5000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/12/2006 Abandoned Material:
Current Age: 17 Abandoned Date:
Install Date: 9/15/2006 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/15/2024 4/15/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 4/15/2024 4/15/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/15/2024 4/15/2025
Overfill Prev Device Overfill Drop Tube Valve 2/21/2022 2/21/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 2/21/2022 2/21/2025
Leak Detect - Piping Sump Sensor 4/15/2024 4/15/2025
Spill Contain Device Single Wall Spill Bucket 2/21/2022 2/21/2025
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test Pass 4/15/2024
Tank Fiberglass Double Wall Precision Test (Tank) Pass 2/26/2019

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/21/2022 2/21/2025
Leak Detect - Piping Sump Sensor 4/15/2024 4/15/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/21/2022 2/21/2025
Leak Detect - Piping Sump Sensor 4/15/2024 4/15/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/21/2022 2/21/2025
Leak Detect - Piping Sump Sensor 4/15/2024 4/15/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 2/21/2022 2/21/2025
Leak Detect - Piping Sump Sensor 4/15/2024 4/15/2025

MFD Motorfuel Dispensing Forms

No Forms Found