Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2042062
Status: Active
Facility Name: FS004 Southwest
Address: 3746 S. Iron St.
Chicago, IL 60609
County: Cook
Property Parcel: 17-32-300-164-0000
Facility Type: City / Town
Owner Type: Municipal
Green Tag Decal: Y002194
Green Tag Issue Date: 12/8/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: City of Chicago Department of Fleet and Facility Management
Owner Address: 30 North LaSalle Street, Suite 300
Chicago, IL 60602
Owner Status: Current Owner
Purchase Date: 11/15/2003
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 6/29/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 12/8/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038288 City of Chicago Department of Fleet and Facility Management Current Owner 11/15/2003
U0025867 City of Chicago Department of Fleet and Facility Management - DO NOT USE Former Owner 3/18/2004

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240746 (Pending)    Issue Date: 3/12/2024    Expiration Date: 5/11/2024    View NOV Form

Tanks Deficiency
1, 2, 3, 4 Annual leak detection certification not completed (Required annually).
1, 2, 3, 4 Document that emergency shut-off (shear valves) are in proper working order
1, 2, 3, 4 Line interstitial sensor functional test not accomplished (Required annually).
1, 2, 3, 4 Mechanical line leak detector requires annual functional test.
Facility Missing copies of Annual Walkthrough Inspection Report.
1, 2, 3, 4 Monthly line interstitial sensor records not available.
1, 2, 3, 4 Required monthly tank interstitial sensor records not available.
1, 2, 3, 4 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2, 4 Tank interstitial sensor functional test not accomplished (Required annually).

NOV Number: E0020240747 (Pending)    Issue Date: 3/12/2024    Expiration Date: 5/11/2024    View NOV Form

Tanks Deficiency
Facility Fire Extinguishers - Past due for annual testing

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/26/2004 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 3/18/2004 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/24/2004

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/3/2024 4/3/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/3/2024 4/3/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/3/2024 4/3/2025
Overfill Prev Device Overfill Drop Tube Valve 2/11/2022 2/11/2025
Piping Fiberglass Chase N/A N/A
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor 4/3/2024 4/3/2025
Spill Contain Device Single Wall Spill Bucket 6/18/2021 6/18/2024
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test Pass 4/3/2024
Piping Fiberglass Secondary Containment Steel primary Precision Test Pass 2/25/2021



Tank Number 2

Capacity: 20000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/26/2004 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 3/18/2004 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/24/2004

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/3/2024 4/3/2025
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/3/2024 4/3/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/3/2024 4/3/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/3/2024 4/3/2025
Overfill Prev Device Overfill Drop Tube Valve 2/11/2022 2/11/2025
Piping Fiberglass Chase N/A N/A
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor 4/3/2024 4/3/2025
Piping Single Wall STP/Tanktop Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor 4/3/2024 4/3/2025
Spill Contain Device Single Wall Spill Bucket 6/18/2021 6/18/2024
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test Pass 4/3/2024
Piping Fiberglass Secondary Containment Steel primary Precision Test Pass 2/25/2021



Tank Number 3

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/26/2004 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 3/18/2004 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/24/2004

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/3/2024 4/3/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/3/2024 4/3/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/3/2024 4/3/2025
Overfill Prev Device Overfill Drop Tube Valve 2/11/2022 2/11/2025
Piping Fiberglass Chase N/A N/A
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor 4/3/2024 4/3/2025
Spill Contain Device Single Wall Spill Bucket 6/18/2021 6/18/2024
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test Pass 4/3/2024
Piping Fiberglass Secondary Containment Steel primary Precision Test Pass 2/25/2021



Tank Number 4

Capacity: 20000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/26/2004 Abandoned Material:
Current Age: 19 Abandoned Date:
Install Date: 3/18/2004 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/24/2004

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/3/2024 4/3/2025
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/3/2024 4/3/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/3/2024 4/3/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/3/2024 4/3/2025
Overfill Prev Device Overfill Drop Tube Valve 2/11/2022 2/11/2025
Piping Fiberglass Chase N/A N/A
Piping Fiberglass Double Wall A.O. Smith N/A N/A
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor 4/3/2024 4/3/2025
Piping Single Wall STP/Tanktop Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor 4/3/2024 4/3/2025
Spill Contain Device Single Wall Spill Bucket 6/18/2021 6/18/2024
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall A.O. Smith Precision Test Pass 4/3/2024
Piping Fiberglass Secondary Containment Steel primary Precision Test Pass 2/25/2021



Tank Number 5

Capacity: 750 Petroleum Use:
Product: Unknown CERCLA Substance:
Status: Pre 1974 CAS Code:
Regulated Status: Exempt Removed Date:
OSFM First Notify Date: 3/30/2021 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 12/13/1973 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/3/2024 4/3/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/3/2024 4/3/2025



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/3/2024 4/3/2025



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/3/2024 4/3/2025



Name\ID 17/18

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/3/2024 4/3/2025



Name\ID 19/20

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/3/2024 4/3/2025



Name\ID 21/22

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/3/2024 4/3/2025



Name\ID 23/24

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/3/2024 4/3/2025



Name\ID 25/26

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/3/2024 4/3/2025



Name\ID 27

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/3/2024 4/3/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/3/2024 4/3/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/3/2024 4/3/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/3/2024 4/3/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 6/18/2021 6/18/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/3/2024 4/3/2025

MFD Motorfuel Dispensing Forms