1, 2 |
Dispensers - hoses cracked, split or worn and require replacement - Replace main hose. |
Facility |
Miscellaneous |
Facility |
Miscellaneous - Emergency shut off switch in control station is blocked by display rack. Move rack so it is not blocked. |
Facility |
Miscellaneous - Emergency shut off switch sign must be installed at control station. " Emergency Shut Off" minimium 2" lettering. |
Facility |
Missing copy of emergency instructions or emergency procedures plan |
1 |
Open electrical conduit or junction boxes. - Premium probe or tank sensor well has open electric. Junction box is missing plugs. Install plugs so electric is sealed. |
1, 2 |
Open electrical conduit or junction boxes. - Under dispenser 7/8 the seal off is missing a plug. Install plug to seal electric. |
1, 2 |
Tank monitor does not appear to function properly and requires maintenance. - Veeder Root shows L7 Fuel Alarm on monitor, but is not in alarm or shown on sensor printout. Repair must be made to clear sensor and make sure Veeder Root goes into alarm. |