Deficiencies (Current)
NOV Number:
E0020241223
(Pending)
Issue Date:
4/24/2024
Expiration Date:
6/23/2024
View NOV Form
Tanks |
Deficiency |
1, 2 |
Line interstitial sensors have been raised and rendered inoperational. - Under dispenser 7/8 |
1, 2 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
1, 2 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Both tank top sumps |
NOV Number:
E0020241224
(Pending)
Issue Date:
4/24/2024
Expiration Date:
6/23/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable |