Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2039882
Status: Active
Facility Name: Circle K #6839
Address: 3153 West 183rd
Homewood, IL 604302806
County: Cook
Property Parcel: 31-01-100-016-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002945
Green Tag Issue Date: 5/10/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: RDK Ventures, LLC
Owner Address: 1100 Situs Court, Suite 100
Raleigh, NC 27606
Owner Status: Current Owner
Purchase Date: 11/7/2011
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/27/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/14/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures, LLC Current Owner 11/7/2011
U0033587 Jetco Properties, Inc. Former Owner 6/2/2006
U0028677 Albertson's, Inc. Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00116-2024UPG Upgrade Approved / Amended 1/30/2024 1/30/2024 7/30/2024 Documents
00241-2024UPG Upgrade Approved / Issued 3/4/2024 3/4/2024 9/4/2024 Documents

Deficiencies (Current)

NOV Number: E0020240599 (Pending)    Issue Date: 3/1/2024    Expiration Date: 4/30/2024    View NOV Form

Tanks Deficiency
1 Annual leak detection certification not completed (Required annually). - ATG failed on 12/26/2023 Repair/replace and retest.
1, 2 Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - Failed on 12/26/2023. Repair/Replace and retest.

NOV Number: E0020241032 (Pending)    Issue Date: 4/9/2024    Expiration Date: 6/8/2024    View NOV Form

Tanks Deficiency
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

NOV Number: E0020241033 (Pending)    Issue Date: 4/9/2024    Expiration Date: 6/8/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shutoff switch form is available at https://sfm.illinois.gov. Perform test and complete form. Maintain form on site.
Facility Control station not equipped with an emergency shutoff switch - Emergency stop at all control stations. 175.210 d)3)
Facility Facility Operation and Maintenance Plan not updated to new requirements. - (Need to up date. ) Facility Operations and Maintenance Plan is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site.
1, 2 Line interstitial sensor functional test not accomplished (Required annually). - Dispenser 1/2 sensor needs to be tested for positive shut down.
1, 2 Line interstitial sensors have been raised and rendered inoperational. - Dispensers 3/4 and 5/6
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
1, 2 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Shear valves/Impact valves. Provide documentation that annual testing of all shear valves has been conducted and passed. Go to https://sfm.illinois.gov to print out the Shear Valve inspection form.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 15000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active

MFD Motorfuel Dispensing Forms