Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2036703
Status: Active
Facility Name: Prarie Material Sales Inc
Address: 835 N Peoria Street
Chicago, IL 60642
County: Cook
Property Parcel:
Facility Type: Industrial / Manufacturing
Owner Type: Private
Green Tag Decal: X002107
Green Tag Issue Date: 9/19/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: VCNA Prairie Illinois Building Products, Inc.
Owner Address: 7601 West 79th Street
Bridgeview, IL 60455
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 6/30/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 9/19/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0034951 VCNA Prairie Illinois Building Products, Inc. Current Owner
U0026880 Prarie Material Sales Inc Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

No Deficiencies Found

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/8/2000 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 1/1/1996 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c 12/19/2023 12/19/2024
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 12/19/2023 12/19/2024
Overfill Prev Device Overfill Drop Tube Valve 12/1/2022 12/1/2025
Piping Fiberglass Double Wall Ameron N/A N/A
Piping STP/Tanktop Sump containment FRP 12/1/2022 12/1/2025
Leak Detect - Piping Sump Sensor 12/14/2022 12/14/2023
Spill Contain Device Single Wall Spill Bucket 12/1/2022 12/1/2025
Tank Fiberglass Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found