Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2036503
Status: Active
Facility Name: Circle K #6712
Address: 1421 North Bridge Street
Yorkville, IL 60560
County: Kendall
Property Parcel: 02-28-104-025
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X000784
Green Tag Issue Date: 5/5/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: RDK Ventures, LLC
Owner Address: 1100 Situs Court, Suite 100
Raleigh, NC 27606
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/27/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/5/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures, LLC Current Owner 1/7/2010
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner
U0027449 Equilon Enterprises, LLC Former Owner
U0013849 Shell Oil Products Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241310 (Pending)    Issue Date: 5/8/2024    Expiration Date: 7/7/2024    View NOV Form

Tanks Deficiency
Facility Facility Operation and Maintenance Plan not completed or available. - Update operations and maintenance plan.
Facility Miscellaneous - Dispenser 9 needs a warning sign posted. Sign needs to be per code. 175.220 a) Minimum signage requires letters shall not be less than 7/8” in height. The top of the sign shall be mounted no higher than 10’ above grade. The wording shall include a minimum of 1) “Warning” 2) “Stop Engine” 3) “No Smoking” 4) “Persons fueling vehicles shall remain with their vehicle, at the nozzle, while fueling is in progress” 5) “It is unlawful and dangerous for anyone to dispense gasoline into unapproved containers”
1 Miscellaneous - STP sump sensor in lying down. Sensor shall be stood up at lowest point of sump or per manufactures specification.
Facility Missing copy of emergency instructions or emergency procedures plan - Update emergency procedures plan.
1, 2 Monthly line interstitial sensor records not available. - Monthly piping sensor reports are not on site for 1/24 thru 3/24. They must be kept on site for all months.
1, 2 Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps.
1, 2 Precision line test required.
1, 2 Precision tank test required.
1, 2 Required monthly tank interstitial sensor records not available. - Monthly tank sensor and CSLD test are not on site for 1/24 thru 3/24. They must be kept on site for all months.
2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill buckets must be kept clean and dry.
2 Tank monitor does not appear to function properly and requires maintenance. - Tank 2 failed annual ATG test. Rerpair must be made and retested. Passing results shall be entered on OSFM portal.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/23/2000 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 7/12/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/13/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/22/2024 4/22/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 4/22/2024 4/22/2025
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 4/22/2024 4/22/2025
Overfill Prev Device Overfill Drop Tube Valve 4/22/2024 4/22/2027
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 4/25/2022 4/25/2025
Leak Detect - Piping Sump Sensor 4/22/2024 4/22/2025
Spill Contain Device Double Wall Spill Bucket 4/22/2024 4/22/2027
Tank Fiberglass Double Wall Fluid Containment Brine Filled N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test Pass 4/22/2024



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/23/2000 Abandoned Material:
Current Age: 23 Abandoned Date:
Install Date: 7/12/2000 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/13/2000

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/22/2024 4/22/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 4/25/2023 4/22/2024
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 4/22/2024 4/22/2025
Overfill Prev Device Overfill Drop Tube Valve 4/22/2024 4/22/2027
Piping Fiberglass Double Wall Ameron N/A N/A
Piping Single Wall STP/Tanktop Sump 4/25/2022 4/25/2025
Leak Detect - Piping Sump Sensor 4/22/2024 4/22/2025
Spill Contain Device Double Wall Spill Bucket 4/22/2024 4/22/2027
Tank Fiberglass Double Wall Fluid Containment Brine Filled N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Precision Test Pass 4/22/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/25/2022 4/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2024 4/22/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/25/2022 4/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2024 4/22/2025



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 4/25/2022 4/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2024 4/22/2025



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 4/25/2022 4/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2024 4/22/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/25/2022 4/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2024 4/22/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 4/25/2022 4/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2024 4/22/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 4/25/2022 4/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2024 4/22/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/25/2022 4/25/2025
Leak Detect - Piping Sump Sensor with positive shutdown 4/22/2024 4/22/2025

MFD Motorfuel Dispensing Forms

No Forms Found