Facility Number: 2035789
Status: Active
Facility Name: (Shell) Veer Petro, Inc.
Address: 300 Dixie Highway
Chicago Heights, IL 60411
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002891
Green Tag Issue Date: 10/19/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Veer Petro, Inc.
Owner Address: 300 Dixie Highway
Chicago Heights, IL 60411
Owner Status: Current Owner
Purchase Date: 12/1/2001
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 5/9/2023

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/9/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033540 Veer Petro, Inc. Current Owner 12/1/2001
U0028411 US Petro Mart Former Owner 9/1/1998
U0033313 Kaur, Rajwinder Former Owner
U0026046 Chicago Heights Natl Bank Trust 1193 Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241247 (Pending)    Issue Date: 4/29/2024    Expiration Date: 6/28/2024    View NOV Form

Tanks Deficiency
Facility Facility Operation and Maintenance Plan not completed or available. - Facility Operations and Maintenance Plan is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site.
Facility Financial responsibility must be reported yearly - Financial Responsibility form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
6, 7, 9, 10 Line interstitial sensors have been raised and rendered inoperational. - All dispensers and both regular STPs.
Facility Miscellaneous - Emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. 175.210 d)3) (Behind Counter)
6 Miscellaneous - Must have lock on Snap cap for Snap caps that are not in a spill bucket.
Facility Missing copy of emergency instructions or emergency procedures plan - Form is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site.
6, 7, 9, 10 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. Must maintain 24 months’ worth. (Liquid Status)
6, 7, 9, 10 Piping interstitial must be open in all sumps - Remove jumper tubing and/or Schrader valves in all STP and dispenser sumps. (All Dispensers and STPs)
9, 10 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
98-1293 6/2/1998 Removal Log 1684-98

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 1000 Petroleum Use:
Product: Fuel Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: State Removed Date: 6/3/1998
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 10/1/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 1000 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 6/3/1998
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 10/1/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 5000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 6/3/1998
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 11/1/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 5000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 6/3/1998
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 11/1/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 6/3/1998
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 11/1/1973 Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/19/2000 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 11/15/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 1/29/2024 1/29/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 1/29/2024 1/29/2025
Overfill Prev Device Overfill Drop Tube Valve 1/29/2024 1/29/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 1/29/2024 1/29/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 7/15/2021 7/15/2022
Leak Detect - Piping Sump Sensor with positive shutdown 1/29/2024 1/29/2025
Spill Contain Device Single Wall Spill Bucket 1/29/2024 1/29/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 1/29/2024



Tank Number 7

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/19/2000 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 11/15/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 1/29/2024 1/29/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 1/29/2024 1/29/2025
Overfill Prev Device Overfill Drop Tube Valve 1/29/2024 1/29/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 1/29/2024 1/29/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 7/15/2021 7/15/2022
Leak Detect - Piping Sump Sensor with positive shutdown 1/29/2024 1/29/2025
Spill Contain Device Single Wall Spill Bucket 1/29/2024 1/29/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 1/29/2024



Tank Number 8

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Does Not Exist CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 9

Capacity: 4000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/17/2017 Abandoned Material:
Current Age: 7 Abandoned Date:
Install Date: 9/9/2016 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 1/29/2024 1/29/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 1/29/2024 1/29/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 1/29/2024 1/29/2025
Overfill Prev Device Overfill Drop Tube Valve 1/29/2024 1/29/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 1/29/2024 1/29/2027
Leak Detect - Piping Non-Discriminating Sump Sensor with positive shutdown 7/15/2021 7/15/2022
Leak Detect - Piping Sump Sensor with positive shutdown 1/29/2024 1/29/2025
Spill Contain Device Single Wall Spill Bucket 1/29/2024 1/29/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 1/29/2024



Tank Number 10

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/17/2017 Abandoned Material:
Current Age: 7 Abandoned Date:
Install Date: 9/9/2016 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 1/29/2024 1/29/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 1/29/2024 1/29/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 1/29/2024 1/29/2025
Overfill Prev Device Overfill Drop Tube Valve 1/29/2024 1/29/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 1/29/2024 1/29/2027
Leak Detect - Piping Non-Discriminating Sump Sensor with positive shutdown 7/15/2021 7/15/2022
Leak Detect - Piping Sump Sensor with positive shutdown 1/29/2024 1/29/2025
Spill Contain Device Single Wall Spill Bucket 1/29/2024 1/29/2027
Tank Fiberglass Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 1/29/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 1/29/2024 1/29/2027
Leak Detect - Piping Sump Sensor 1/29/2024 1/29/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 1/29/2024 1/29/2027
Leak Detect - Piping Sump Sensor 1/29/2024 1/29/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 1/29/2024 1/29/2027
Leak Detect - Piping Sump Sensor 1/29/2024 1/29/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Double Wall UDC Sump 1/29/2024 1/29/2027
Leak Detect - Piping Sump Sensor 1/29/2024 1/29/2025

MFD Motorfuel Dispensing Forms

No Forms Found