Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2035789
Status: Active
Facility Name: (Shell) Veer Petro, Inc.
Address: 300 Dixie Highway
Chicago Heights, IL 60411
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002891
Green Tag Issue Date: 10/19/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Veer Petro, Inc.
Owner Address: 300 Dixie Highway
Chicago Heights, IL 60411
Owner Status: Current Owner
Purchase Date: 12/1/2001
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 5/9/2023

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/9/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033540 Veer Petro, Inc. Current Owner 12/1/2001
U0028411 US Petro Mart Former Owner 9/1/1998
U0033313 Kaur, Rajwinder Former Owner
U0026046 Chicago Heights Natl Bank Trust 1193 Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241247 (Pending)    Issue Date: 4/29/2024    Expiration Date: 6/28/2024    View NOV Form

Tanks Deficiency
Facility Facility Operation and Maintenance Plan not completed or available. - Facility Operations and Maintenance Plan is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site.
Facility Financial responsibility must be reported yearly - Financial Responsibility form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
6, 7, 9, 10 Line interstitial sensors have been raised and rendered inoperational. - All dispensers and both regular STPs.
Facility Miscellaneous - Emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. 175.210 d)3) (Behind Counter)
6 Miscellaneous - Must have lock on Snap cap for Snap caps that are not in a spill bucket.
Facility Missing copy of emergency instructions or emergency procedures plan - Form is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site.
6, 7, 9, 10 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. Must maintain 24 months’ worth. (Liquid Status)
6, 7, 9, 10 Piping interstitial must be open in all sumps - Remove jumper tubing and/or Schrader valves in all STP and dispenser sumps. (All Dispensers and STPs)
9, 10 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
98-1293 6/2/1998 Removal Log 1684-98

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 1000 Fuel Oil Removed State 06/03/1998 - REM
2 1000 Used Oil Removed Exempt 06/03/1998 - REM
3 5000 Gasoline Removed Exempt 06/03/1998 - REM
4 5000 Gasoline Removed Exempt 06/03/1998 - REM
5 8000 Gasoline Removed Exempt 06/03/1998 - REM
6 12000 Gasoline - Regular Currently in use Federal $0.00
7 8000 Gasoline - Regular Currently in use Federal $0.00
8 6000 Diesel Fuel Does Not Exist Federal
9 4000 Gasoline - Premium Currently in use Federal $0.00
10 4000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
5/6 Active
1/2 Active
3/4 Active
7/8 Active

MFD Motorfuel Dispensing Forms