Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2035227
Status: Active
Facility Name: Cyto Real Estate, Inc.
Address: 7600 W. North Ave.
Elmwood Park, IL 60607
County: Cook
Property Parcel: 12-36-329-075-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X001566
Green Tag Issue Date: 12/22/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Cyto Real Estate, Inc.
Owner Address: 7600 W. North Avenue
Elmwood Park, IL 60707
Owner Status: Current Owner
Purchase Date: 10/27/2021
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 11/19/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 12/22/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040466 Cyto Real Estate, Inc. Current Owner 10/27/2021
U0032360 Angel Associates, LP Former Owner 12/16/2009
U0039775 Margaret M. Dunlap Trust Former Owner 3/28/1994
U0027493 Amoco Oil Company Former Owner 1/1/1985
U0000552 BP Products North America, Inc. Former Owner 1/1/1985
U0036449 Chandy, Cyriac Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241176 (Pending)    Issue Date: 4/16/2024    Expiration Date: 6/15/2024    View NOV Form

Tanks Deficiency
Facility Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable

NOV Number: E0020241178 (Pending)    Issue Date: 4/16/2024    Expiration Date: 6/15/2024    View NOV Form

Tanks Deficiency
1, 2, 3 Miscellaneous - Impressed current hour meter not working
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1 Submit Notification Form for Product Change - Tank 1 is listed as containing regular unleaded fuel. Submit notification change form to change product to Diesel. https://webapps.sfm.illinois.gov/USTPortal/NotificationForm

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
91-2113 Eligible 7/25/1996 8/23/1996 $10,000
91-1786 Eligible 7/25/1996 8/23/1996 $10,000
89-2723 Eligible 7/25/1996 8/23/1996 $10,000
20180994 Eligible 4/2/2020 4/2/2020 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 39 Abandoned Date:
Install Date: 1/1/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1985

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 12/13/2023 12/13/2024
Corrosion Prot - Tank Impressed Current Cathodic Protection 12/13/2023 12/13/2024
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/12/2023 10/12/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root EMC with CSLD 10/12/2023 10/12/2024
Overfill Prev Device Overfill Drop Tube Valve 10/20/2022 10/20/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 10/20/2022 10/20/2025
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test Pass 10/12/2023
Tank STIP3 Single Wall Precision Test (Tank) Pass 12/21/2020



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 39 Abandoned Date:
Install Date: 1/1/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1985

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 12/13/2023 12/13/2024
Corrosion Prot - Tank Impressed Current Cathodic Protection 12/13/2023 12/13/2024
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/12/2023 10/12/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root EMC with CSLD 10/12/2023 10/12/2024
Overfill Prev Device Overfill Drop Tube Valve 10/20/2022 10/20/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 10/20/2022 10/20/2025
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test Pass 10/12/2023



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 39 Abandoned Date:
Install Date: 1/1/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1985

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 12/13/2023 12/13/2024
Corrosion Prot - Tank Impressed Current Cathodic Protection 12/13/2023 12/13/2024
Leak Detect - Piping Electronic Pressurized Line Leak Detection 10/12/2023 10/12/2024
Leak Detect - Tank Automatic Tank Gauging Veeder Root EMC with CSLD 10/12/2023 10/12/2024
Overfill Prev Device Overfill Drop Tube Valve 10/20/2022 10/20/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 10/20/2022 10/20/2025
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test Pass 10/12/2023



Tank Number 4

Capacity: 550 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/5/2018
OSFM First Notify Date: 4/25/1986 Abandoned Material:
Current Age: 33 Abandoned Date:
Install Date: 1/1/1985 Red Tag Issue Date:
Last Used Date: 7/7/2012 Fee Due: $0.00
Product Date: 1/1/1985

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 9/8/2017 9/8/2018
Corrosion Prot - Tank Impressed Current Cathodic Protection 9/8/2017 9/8/2018
Leak Detect - Piping Gravity Feed N/A N/A
Leak Detect - Tank 110 - 600 gallons Manual Tank Gauging N/A N/A
Overfill Prev Device Less than 25 gallon fills N/A N/A
Piping Fiberglass Double Wall N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank STIP3 Single Wall N/A N/A
Vent, Riser, Fill Piping Steel risers N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found