1 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Steel lid is bent and deteriorating. |
1 |
Line leak detection equipment in alarm or failed test, must repair or replace. - L1: (Unleaded Motor Sump) Fuel Alarm.
Current alarm has been on since at least Feb 1. Fuel alarm has been on periodically since at least April 2023. |
1, 2 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
1 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP sump(s) contain(s) liquid. Remove liquid and repair containment to prevent further liquid ingress. |