Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2029965
Status: Active
Facility Name: Bala Insha, Inc.
Address: 1503 North Broadway Avenue
Melrose Park, IL 60160
County: Cook
Property Parcel: 15-03-130-033
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X001490
Green Tag Issue Date: 8/4/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Melrose 1503 Property, LLC
Owner Address: 2052 DeCook
Park Ridge, IL 60068
Owner Status: Current Owner
Purchase Date: 3/16/2022
Type of Financial Responsibility:
Financial Responsibility Reporting Due Date:

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/1/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041203 Melrose 1503 Property, LLC Current Owner 3/16/2022
U0019449 Midwest Bank & Trust Serv. #80-05-3340 Former Owner 6/21/1988

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240783 (Pending)    Issue Date: 3/14/2024    Expiration Date: 5/13/2024    View NOV Form

Tanks Deficiency
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (ATG) not completed. Testing shall be completed and submitted to OSFM.
1, 2 Annual line precision and mechanical line leak detector functional test not completed.
1, 2 Annual tank impressed current system test not completed.
Facility Facility Operation and Maintenance Plan not completed or available. - Facility Operations and Maintenance Plan does not meet requirements of new rules. Go to www.sfm.illinois.gov to download and complete O & M template and maintain completed form on site.
Facility Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually; The form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility
Facility Missing copies of 30 day Walkthrough Inspection Report.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website.
Facility Missing list of designated Class A/B & C Operators - Copies of all current Class A/B testing certificates shall be maintained on file on site. Copies of all current Class C testing certificates shall be maintained on file on site. A comprehensive list of Class A / B / C Operator(s) shall be maintained on site and must be current.
1, 2 Monthly impressed current log not available or maintained.
1, 2 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
1, 2 Precision tank test required.
1, 2 Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG. Must maintain 24 months’ worth.
1, 2 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
Facility Submit Notification Form For Ownership Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of an ownership change.
1, 2 Triennial spill prevention equipment testing not completed.

NOV Number: E0020240784 (Pending)    Issue Date: 3/14/2024    Expiration Date: 5/13/2024    View NOV Form

Tanks Deficiency
Facility Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable
Facility Fire Extinguishers - Past due for annual testing

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
98-2022 Eligible 10/1/2001 10/9/2001 $100,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/8/1992 Abandoned Material:
Current Age: 46 Abandoned Date:
Install Date: 1/20/1978 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 5/6/2024 5/6/2025
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/6/2024 5/6/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/6/2024 5/6/2025
Overfill Prev Device Overfill Drop Tube Valve 5/6/2024 5/6/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/6/2024 5/6/2027
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 5/6/2024
Piping Steel Single Wall Piping Precision Test Pass 10/19/2021
Tank Steel Single Wall Precision Test (Tank) Pass 5/6/2024



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/8/1992 Abandoned Material:
Current Age: 46 Abandoned Date:
Install Date: 1/20/1978 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Isolation Boots Flex Connector N/A N/A
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 5/6/2024 5/6/2025
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 5/6/2024 5/6/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/6/2024 5/6/2025
Overfill Prev Device Overfill Drop Tube Valve 5/6/2024 5/6/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/6/2024 5/6/2027
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 5/6/2024
Piping Steel Single Wall Piping Precision Test Pass 10/19/2021
Tank Steel Single Wall Precision Test (Tank) Pass 5/6/2024



Tank Number 3

Capacity: 550 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Pre 1974 CAS Code:
Regulated Status: Exempt Removed Date:
OSFM First Notify Date: 5/8/1992 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 1/1/1960 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 500 Petroleum Use:
Product: Heating Oil CERCLA Substance:
Status: Pre 1974 CAS Code:
Regulated Status: Exempt Removed Date:
OSFM First Notify Date: 12/31/1998 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 1/1/1960 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found