Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2029682
Status: Active
Facility Name: Administration Building
Address: 2700 Ogden Avenue
Downers Grove, IL 60515
County: Du Page
Property Parcel:
Facility Type: State
Owner Type: State
Green Tag Decal: X000654
Green Tag Issue Date: 12/8/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Illinois State Toll Highway Authority
Owner Address: 2700 Ogden Avenue
Downers Grove, IL 60515
Owner Status: Current Owner
Purchase Date: 6/19/1992
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 12/27/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 8/25/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0007425 Illinois State Toll Highway Authority Current Owner 6/19/1992

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020241164 (Pending)    Issue Date: 4/18/2024    Expiration Date: 6/17/2024    View NOV Form

Tanks Deficiency
1, 2 Annual electronic line leak detector test not completed.
1, 2 Annual leak detection certification not completed (Required annually).
1, 2 Line interstitial sensor functional test not accomplished (Required annually).
Facility Missing copies of 30 day Walkthrough Inspection Report. - Have not filled out February nor March
Facility Missing copies of Annual Walkthrough Inspection Report. - Completed by your contractor on the annual testing
1, 2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/9/1993 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 7/8/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/10/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/7/2023 4/7/2024
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 4/7/2023 4/7/2024
Overfill Prev Device Overfill Alarm 11/16/2021 11/16/2024
Overfill Prev Device Overfill Drop Tube Valve 11/16/2021 11/16/2024
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 11/16/2021 11/16/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/7/2023 4/7/2024
Leak Detect - Piping Non-Discriminating Sump Sensor 4/7/2023 4/7/2024
Spill Contain Device Single Wall Spill Bucket 11/16/2021 11/16/2024
Tank Fiberglass Brine Filled Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 4/23/2020
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 4/7/2023



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/9/1993 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 7/8/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/15/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/7/2023 4/7/2024
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors with monitor 4/7/2023 4/7/2024
Overfill Prev Device Overfill Alarm 11/16/2021 11/16/2024
Overfill Prev Device Overfill Drop Tube Valve 11/16/2021 11/16/2024
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 11/16/2021 11/16/2024
Leak Detect - Piping Non-Discriminating Sump Sensor 11/29/2022 11/29/2023
Leak Detect - Piping Sump Sensor with positive shutdown 4/7/2023 4/7/2024
Spill Contain Device Single Wall Spill Bucket 11/16/2021 11/16/2024
Tank Fiberglass Brine Filled Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/7/2023 4/7/2026
Leak Detect - Piping Sump Sensor with positive shutdown 4/7/2023 4/7/2024



Name\ID 2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 11/16/2021 11/16/2024
Leak Detect - Piping Sump Sensor with positive shutdown 4/7/2023 4/7/2024

MFD Motorfuel Dispensing Forms

No Forms Found