Facility |
A/B operator retraining required as a result of issuance of the Notice of Violation - Primary A / B certified operator shall be retrained as a result of NOV being issued. |
2, 3, 4 |
Annual line precision and mechanical line leak detector functional test not completed. - Annual third party precision line test is required. Records showing passing tests shall be available for review by OSFM Inspector.
Annual third party testing required on all line leak detectors. Records showing passing tests shall be available for review by OSFM Inspector. |
1, 2, 3, 4, 6 |
Annual piping impressed current test not completed. - Annual third party testing required on impressed current system. Perform annual testing and maintain passing documentation on site for review by OSFM Inspector. |
6 |
Annual tank impressed current system test not completed. - Annual third party testing required on impressed current system. Perform annual testing and maintain passing documentation on site for review by OSFM Inspector. |
1, 2, 3, 4, 6 |
Failed to Empty the Tank to 1" or Less - All Tanks are currently not in service and shall be pumped down to one inch or less of product. |
Facility |
Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually; declaration form can be found at www.sfm.illinois.gov (in Commercial section, click UST Applications and Forms, then Financial Responsibility Report). Complete form online and submit electronically. |
Facility |
Missing copies of current testing certificates for operator training - Copies of all current Class A/B testing certificates shall be maintained on file on site.
Copies of all current Class C testing certificates shall be maintained on file on site. |
Facility |
Missing copies of quarterly inspection checklist - Quarterly Equipment Inspection Checklist/Operations & Maintenance Guidelines shall be performed and recorded on appropriate checklist form and maintained on site for review by OSFM inspector. The checklist template is available on the OSFM website. |
Facility |
Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website. |
Facility |
Missing copy of written UST facility operation & maintenance plan - Adopt and implement a written operations and maintenance plan, signed by both the owner and either a Class A or Class B Operator designated for the UST facility An Operations & Maintenance template is available on the OSFM website. |
Facility |
Missing list of designated Class A/B & C Operators - A comprehensive list of Class A / B / C Operator(s) shall be posted and maintained on site. |
6 |
Monthly impressed current log not available or maintained. - A log showing the rectifier gauge readings from Impressed Current rectifier shall be maintained monthly on site for review by OSFM Inspector. Log shall show date; amp, volt and hour meter readings; who recorded information. |
1, 2, 3, 4, 6 |
Monthly impressed current system log not available or maintained. - A log showing the rectifier gauge readings from Impressed Current rectifier shall be maintained monthly on site for review by OSFM Inspector. Log shall show date; amp, volt and hour meter readings; who recorded information. |
2, 3, 4 |
Precision tank test required. - Maintain one normal tank leak report per tank for past 24 months. If you do not have these tank leak reports a tank tightness test is required. |
1 |
Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - Please remove Tank # 1. |
2, 3, 4 |
Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG. |
1, 2, 3, 4 |
Shear valves not at grade level - Shear valves appear to be installed improperly; shear valves shall be installed to manufacturer's specifications. |
2, 3, 4 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill Bucket(s) contain(s) liquid and/or debris; remove liquid/debris and maintain clean and dry at all times. |