Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2028125
Status: Inactive
Facility Name: former Rolling Meadows Auto Clinic
Address: 850 E. Northwest Hwy.
Palatine, IL 60067
County: Cook
Property Parcel: 02-24-106-007-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Q001635
Green Tag Issue Date: 6/15/2015
Green Tag Expiration Date: 12/31/2017

Owner Details

Owner Name: AZ SPE, LLC
Owner Address: 12346 S. Keeler Ave.
Alsip, IL 60803
Owner Status: Current Owner
Purchase Date: 6/29/2017
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/22/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/21/2015 12/31/2017

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037844 AZ SPE, LLC Current Owner 6/29/2017
U0029773 Sandhu Petroleum, Inc. Former Owner 4/1/2010
U0032792 D & D Petroleum, Inc. Former Owner 1/1/2005
U0017925 Palatine Oil Co Former Owner 10/9/1991
U0029826 Suburban Marathon of Palatine, Inc. Former Owner 1/1/1988
U0017927 Harris Bank Palatine Trust #5489 Former Owner 1/1/1988
U0009659 Marathon Petroleum Company LP Former Owner 12/31/1967
U0028166 TCF National Bank Illinois Former Owner
U0027998 Harris Bank Palatine Trustee Trst #5489 Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020161781 (Referred to Legal)    Issue Date: 5/27/2016    Expiration Date: 7/26/2016    View NOV Form

Tanks Deficiency
Facility A/B operator retraining required as a result of issuance of the Notice of Violation - Primary A / B certified operator shall be retrained as a result of NOV being issued.
2, 3, 4 Annual line precision and mechanical line leak detector functional test not completed. - Annual third party precision line test is required. Records showing passing tests shall be available for review by OSFM Inspector. Annual third party testing required on all line leak detectors. Records showing passing tests shall be available for review by OSFM Inspector.
2, 3, 4 Annual piping impressed current test not completed. - Annual third party testing required on impressed current system. Perform annual testing and maintain passing documentation on site for review by OSFM Inspector.
2, 3, 4 Failed to Empty the Tank to 1" or Less - Please empty all the Tanks to 1" or less.
Facility Missing copies of current testing certificates for operator training - Copies of all current Class A/B testing certificates shall be maintained on file on site. Copies of all current Class C testing certificates shall be maintained on file on site.
Facility Missing copies of quarterly inspection checklist - Quarterly Equipment Inspection Checklist/Operations & Maintenance Guidelines shall be performed and recorded on appropriate checklist form and maintained on site for review by OSFM inspector. The checklist template is available on the OSFM website.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website.
Facility Missing copy of written UST facility operation & maintenance plan - Adopt and implement a written operations and maintenance plan, signed by both the owner and either a Class A or Class B Operator designated for the UST facility An Operations & Maintenance template is available on the OSFM website.
Facility Missing list of designated Class A/B & C Operators - A comprehensive list of Class A / B / C Operator(s) shall be posted and maintained on site.
2, 3, 4 Monthly impressed current system log not available or maintained. - A log showing the rectifier gauge readings from Impressed Current rectifier shall be maintained monthly on site for review by OSFM Inspector. Log shall show date; amp, volt and hour meter readings; who recorded information.
1 Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - Please remove Tank # 1.
2, 3, 4 Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG.
2, 3, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill Bucket(s) contain(s) liquid and/or debris; remove liquid/debris and maintain clean and dry at all times.
2, 3, 4 Submit Notification Form For Tank Status Change - Please place these Tanks Out of Service.
2, 3, 4 Tank precision test required. - Maintain one normal tank leak report per tank for past 24 months. If you do not have these tank leak reports a tank tightness test is required.

NOV Number: E0020162699 (Formal)    Issue Date: 8/22/2016    Expiration Date: 10/21/2016    View NOV Form

Tanks Deficiency
Facility A/B operator retraining required as a result of issuance of the Notice of Violation - Primary A / B certified operator shall be retrained as a result of NOV being issued.
2, 3, 4 Annual line precision and mechanical line leak detector functional test not completed. - Annual third party precision line test is required. Records showing passing tests shall be available for review by OSFM Inspector. Annual third party testing required on all line leak detectors. Records showing passing tests shall be available for review by OSFM Inspector.
1, 2, 3, 4, 6 Annual piping impressed current test not completed. - Annual third party testing required on impressed current system. Perform annual testing and maintain passing documentation on site for review by OSFM Inspector.
6 Annual tank impressed current system test not completed. - Annual third party testing required on impressed current system. Perform annual testing and maintain passing documentation on site for review by OSFM Inspector.
1, 2, 3, 4, 6 Failed to Empty the Tank to 1" or Less - All Tanks are currently not in service and shall be pumped down to one inch or less of product.
Facility Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually; declaration form can be found at www.sfm.illinois.gov (in Commercial section, click UST Applications and Forms, then Financial Responsibility Report). Complete form online and submit electronically.
Facility Missing copies of current testing certificates for operator training - Copies of all current Class A/B testing certificates shall be maintained on file on site. Copies of all current Class C testing certificates shall be maintained on file on site.
Facility Missing copies of quarterly inspection checklist - Quarterly Equipment Inspection Checklist/Operations & Maintenance Guidelines shall be performed and recorded on appropriate checklist form and maintained on site for review by OSFM inspector. The checklist template is available on the OSFM website.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website.
Facility Missing copy of written UST facility operation & maintenance plan - Adopt and implement a written operations and maintenance plan, signed by both the owner and either a Class A or Class B Operator designated for the UST facility An Operations & Maintenance template is available on the OSFM website.
Facility Missing list of designated Class A/B & C Operators - A comprehensive list of Class A / B / C Operator(s) shall be posted and maintained on site.
6 Monthly impressed current log not available or maintained. - A log showing the rectifier gauge readings from Impressed Current rectifier shall be maintained monthly on site for review by OSFM Inspector. Log shall show date; amp, volt and hour meter readings; who recorded information.
1, 2, 3, 4, 6 Monthly impressed current system log not available or maintained. - A log showing the rectifier gauge readings from Impressed Current rectifier shall be maintained monthly on site for review by OSFM Inspector. Log shall show date; amp, volt and hour meter readings; who recorded information.
2, 3, 4 Precision tank test required. - Maintain one normal tank leak report per tank for past 24 months. If you do not have these tank leak reports a tank tightness test is required.
1 Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - Please remove Tank # 1.
2, 3, 4 Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG.
1, 2, 3, 4 Shear valves not at grade level - Shear valves appear to be installed improperly; shear valves shall be installed to manufacturer's specifications.
2, 3, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Spill Bucket(s) contain(s) liquid and/or debris; remove liquid/debris and maintain clean and dry at all times.

NOV Number: E0020171109 (Formal)    Issue Date: 4/6/2017    Expiration Date: 6/5/2017    View NOV Form

Tanks Deficiency
1, 2, 3, 4 Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - Please remove these Tanks.

NOV Number: E0020172920 (Referred to Legal)    Issue Date: 10/12/2017    Expiration Date: 12/11/2017    View NOV Form

Tanks Deficiency
1, 2, 3, 4, 6 Annual tank impressed current system appears not to be operational. - The rectifier is turned off.
1, 2, 3, 4, 6 Piping impressed current system appears not to be operational. - The rectifier is turned off.

NOV Number: E0020201093 (Referred to Legal)    Issue Date: 5/13/2020    Expiration Date: 7/12/2020    View NOV Form

Tanks Deficiency
1, 2, 3, 4, 6 Remove tank(s) - Corrosion Protection not Maintained - TANKS MUST BE REMOVED
1, 2, 3, 4, 6 Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - TANKS MUST BE REMOVED

NOV Number: E0020212801 (Referred to Legal)    Issue Date: 10/13/2021    Expiration Date: 12/12/2021    View NOV Form

Tanks Deficiency
1, 2, 3, 4, 6 Failed to Empty the Tank to 1" or Less - Tanks are currently not in service and shall be pumped down to one inch or less of product.
Facility Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually; declaration form can be found at www.sfm.illinois.gov (in Search window, type UST Forms, Click Enter; click UST Applications and Forms; click on Financial Responsibility Report). Complete form online and submit electronically.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
13-1299 Eligible 2/6/2014 3/11/2014 $5,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 6000 Gasoline Condemned Tank Federal 10/14/2021 $0.00
2 6000 Gasoline Condemned Tank Federal 10/14/2021 $0.00
3 8000 Gasoline Condemned Tank Federal 10/14/2021 $0.00
4 10000 Gasoline Condemned Tank Federal 10/14/2021 $0.00
5 550 Used Oil Removed Federal $0.00 05/01/1989 - REM
6 1000 Used Oil Condemned Tank Federal 10/14/2021 $0.00

Dispenser Information

Name\ID Status

MFD Motorfuel Dispensing Forms

No Forms Found