Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2026366
Status: Active
Facility Name: St. Alexius Medical Center
Address: 1555 N. Barrington Road
Hoffman Estates, IL 60194
County: Cook
Property Parcel: 07-07-300-025-0000
Facility Type: Hospital
Owner Type: Private
Green Tag Decal: X004076
Green Tag Issue Date: 4/26/2023
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: St. Alexius Medical Center
Owner Address: 1555 Barrington Road
Hoffman Estates, IL 60194
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/8/2023

Motor Fuel Dispensing Permits

No MFD Permits Found

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0028656 St. Alexius Medical Center Current Owner
U0023398 Hoffman Estates Medical Center Former Owner 1/1/1979
U0007123 Humana, Inc. Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

No Deficiencies Found

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
12-0742 8/14/2012 Removal Log 00742-2012REM
15-0433 5/4/2015 Removal Log 00354-2015REM
92-2261 8/18/1992 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
12-0742 Eligible 10/22/2012 10/22/2012 $5,000
15-0433 Eligible 4/1/2016 5/4/2016 $5,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 1500 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/18/1992
OSFM First Notify Date: 10/29/1990 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 9/1/1979 Red Tag Issue Date:
Last Used Date: 8/18/1992 Fee Due: $0.00
Product Date: 9/1/1979

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 3000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/14/2012
OSFM First Notify Date: 8/11/1992 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 2/1/1992 Red Tag Issue Date:
Last Used Date: 7/20/2012 Fee Due: $0.00
Product Date: 4/15/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 4/3/2008 4/3/2011
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Piping Sump Sensor
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300c
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank STIP3 Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors Sensor Functional Pass 4/18/2008
Leak Detect - Piping Sump Sensor Sensor Functional Pass 4/18/2008



Tank Number 3

Capacity: 20000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/4/2015
OSFM First Notify Date: 8/11/1992 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: 7/15/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/20/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 6/19/2013 6/19/2016
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/3/2014 4/3/2015
Leak Detect - Piping Sump Sensor 4/3/2014 4/3/2015
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350
Overfill Prev Device Overfill Drop Tube Valve
Piping Fiberglass Double Wall N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank STIP3 Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 3000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/2/2012 Abandoned Material:
Current Age: 11 Abandoned Date:
Install Date: 8/15/2012 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 8/15/2012

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 3/13/2024 3/13/2025
Overfill Prev Device Overfill Drop Tube Valve 10/18/2022 10/18/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Non-Discriminating Sump Sensor with positive shutdown 2/10/2023 2/10/2024
Leak Detect - Piping Piping Sump Sensors Not Regulated N/A N/A
Spill Contain Device Single Wall Spill Bucket 10/18/2022 10/18/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 2/10/2023



Tank Number 5

Capacity: 20000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/3/2015 Abandoned Material:
Current Age: 8 Abandoned Date:
Install Date: 5/11/2015 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/10/2015

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Other Non-vented check valve N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 3/13/2024 3/13/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors With Monitor 3/13/2024 3/13/2025
Overfill Prev Device Overfill Drop Tube Valve 8/18/2022 8/18/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 2/10/2023 2/10/2026
Leak Detect - Piping Sump Sensor with positive shutdown 3/13/2024 3/13/2025
Piping Single Wall Transition Sump 8/18/2022 8/18/2025
Leak Detect - Piping Sump Sensor with positive shutdown 3/13/2024 3/13/2025
Spill Contain Device Single Wall Spill Bucket 8/18/2022 8/18/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 3/13/2024

Dispenser Information



MFD Motorfuel Dispensing Forms

No Forms Found