Deficiencies (Current)
NOV Number:
E0020231484
(Pending)
Issue Date:
6/28/2023
Expiration Date:
8/27/2023
View NOV Form
Tanks |
Deficiency |
4, 5, 6, 7 |
Tank monitor does not appear to function properly and requires maintenance. - Yellow and green lights are out and need to be replaced or repaired. |
NOV Number:
E0020240505
(Pending)
Issue Date:
2/22/2024
Expiration Date:
4/22/2024
View NOV Form
Tanks |
Deficiency |
6 |
Miscellaneous - I'm unable to open STP sump lid. It is wedged. ATG is in alarm showing liquid in sump. |
4, 5, 6, 7 |
Tank monitor does not appear to function properly and requires maintenance. - ATG is in alarm. L2 Fuel Alarm and L16 Fuel Alarm. Repair must be made and ATG clear of alarms. Unable to open Regular West STP sump lid (L2 Alarm). |
4, 5, 6 |
Water in dispenser containment with interstitial sensors - Remove water and repair containments to prevent water ingress - Dispenser 15/16 has liquid in sump. Repair must be made to prevent liquid from entering and ATG cleared. |