Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2026015
Status: Active
Facility Name: Thornton Oil Corporation 2
Address: 2 N. Barrington Rd.
Streamwood, IL 60107
County: Cook
Property Parcel: 06-13-403-012-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001498
Green Tag Issue Date: 7/20/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Thornton's LLC
Owner Address: 2600 James Thornton Way
Louisville, KY 40245
Owner Status: Current Owner
Purchase Date: 2/11/2019
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 5/9/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 7/20/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039521 Thornton's LLC Current Owner 2/11/2019
U0014995 Thornton's, Inc. - DO NOT USE THIS OWNER ID Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
01464-2023UPG Upgrade Approved / Issued 12/13/2023 12/13/2023 6/13/2024 Documents

Deficiencies (Current)

No Deficiencies Found

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/4/1990 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 7/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2024 4/8/2025
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/8/2024 4/8/2025
Overfill Prev Device Overfill Drop Tube Valve 4/24/2022 4/24/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 4/8/2024 4/8/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 7/5/2016 7/5/2017
Leak Detect - Piping Non-Discriminating Sump Sensor 7/24/2017 7/24/2018
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025
Piping Single Wall STP/Tanktop Sump 4/8/2024 4/8/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025
Spill Contain Device Double Wall Spill Bucket 5/6/2021 4/8/2024
Tank Fiberglass Single Wall Owens Corning N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Siphon Bar Functional Pass 4/8/2024
Piping Single Wall Transition Sump None Pass 5/6/2021
Tank Fiberglass Single Wall Precision Test (Tank) Pass 4/24/2022
Tank Fiberglass Single Wall Owens Corning Precision Test (Tank) Pass 4/8/2024



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/4/1990 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 7/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2024 4/8/2025
Leak Detect - Piping Siphon Bar N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/8/2024 4/8/2025
Overfill Prev Device Overfill Drop Tube Valve 8/23/2023 8/23/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 4/8/2024 4/8/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025
Piping Single Wall STP/Tanktop Sump 4/8/2024 4/8/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 7/5/2016 7/5/2017
Leak Detect - Piping Non-Discriminating Sump Sensor 7/24/2017 7/24/2018
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025
Spill Contain Device Double Wall Spill Bucket 4/8/2024 4/8/2027
Tank Fiberglass Single Wall Owens Corning N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Leak Detect - Piping Siphon Bar Functional Pass 4/8/2024
Piping Single Wall Transition Sump None Pass 5/6/2021
Tank Fiberglass Single Wall Precision Test (Tank) Pass 4/24/2022
Tank Fiberglass Single Wall Owens Corning Precision Test (Tank) Pass 4/8/2024



Tank Number 3

Capacity: 12000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/4/1990 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 7/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2024 4/8/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/8/2024 4/8/2025
Overfill Prev Device Overfill Drop Tube Valve 4/24/2022 4/24/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 4/8/2024 4/8/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 7/5/2016 7/5/2017
Leak Detect - Piping Non-Discriminating Sump Sensor 7/24/2017 7/24/2018
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025
Spill Contain Device Double Wall Spill Bucket 5/6/2021 4/8/2024
Tank Fiberglass Single Wall Owens Corning N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Fiberglass Single Wall Precision Test (Tank) Pass 4/24/2022
Tank Fiberglass Single Wall Owens Corning Precision Test (Tank) Pass 4/8/2024



Tank Number 4

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/4/1990 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 7/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2024 4/8/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/8/2024 4/8/2025
Overfill Prev Device Overfill Drop Tube Valve 4/24/2022 4/24/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 4/8/2024 4/8/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 7/5/2016 7/5/2017
Leak Detect - Piping Non-Discriminating Sump Sensor 7/24/2017 7/24/2018
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025
Spill Contain Device Double Wall Spill Bucket 4/8/2024 4/8/2027
Tank Fiberglass Single Wall Owens Corning N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Fiberglass Single Wall Precision Test (Tank) Pass 4/24/2022
Tank Fiberglass Single Wall Owens Corning Precision Test (Tank) Pass 4/8/2024
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 11/4/2009



Tank Number 5

Capacity: 6000 Petroleum Use:
Product: Kerosene CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/4/1990 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 7/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2024 4/8/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/8/2024 4/8/2025
Overfill Prev Device Overfill Drop Tube Valve 4/24/2022 4/24/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 4/8/2024 4/8/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 7/5/2016 7/5/2017
Leak Detect - Piping Non-Discriminating Sump Sensor 7/24/2017 7/24/2018
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025
Spill Contain Device Double Wall Spill Bucket 4/8/2024 4/8/2027
Tank Fiberglass Single Wall Owens Corning N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test Pass 12/11/2019
Tank Fiberglass Single Wall Precision Test (Tank) Pass 4/24/2022
Tank Fiberglass Single Wall Owens Corning Precision Test (Tank) Pass 4/8/2024
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 11/4/2009



Tank Number 6

Capacity: 12000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 6/8/2016 Abandoned Material:
Current Age: 8 Abandoned Date:
Install Date: 3/30/2016 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 4/4/2016

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 4/8/2024 4/8/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/8/2024 4/8/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 4/8/2024 4/8/2025
Overfill Prev Device Overfill Drop Tube Valve 4/24/2022 4/24/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 4/8/2024 4/8/2027
Leak Detect - Piping Non-Discriminating Sump Sensor 7/24/2017 7/24/2018
Leak Detect - Piping Non-Discriminating Sump Sensor 7/10/2019 7/10/2020
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025
Spill Contain Device Double Wall Spill Bucket 5/6/2021 4/8/2024
Tank Fiberglass Brine Filled Double Wall Containment Solutions N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Fiberglass Brine Filled Double Wall Containment Solutions Precision Test (Tank) Pass 4/8/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/8/2024 4/8/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/8/2024 4/8/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/8/2024 4/8/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/8/2024 4/8/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025



Name\ID 17

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/8/2024 4/8/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/8/2024 4/8/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/8/2024 4/8/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/8/2024 4/8/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 4/8/2024 4/8/2027
Leak Detect - Piping Sump Sensor with positive shutdown 4/8/2024 4/8/2025

MFD Motorfuel Dispensing Forms

No Forms Found