Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2025063
Status: Active
Facility Name: Alden Quick Mart
Address: 16420 Route 173
Alden, IL 60033
County: McHenry
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X003352
Green Tag Issue Date: 8/16/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Raj Handa
Owner Address: 375 Oakwood Lane
Lake Geneva, WI 53147
Owner Status: Current Owner
Purchase Date: 10/1/2001
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 3/18/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/3/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035158 Handa, Raj Current Owner 10/1/2001
U0026362 Kopulos James Former Owner 5/15/1996
U0009499 Jimmy's Country Station Former Owner 4/1/1996
U0009499 Jimmy's Country Station Former Owner 12/31/1967
U0000336 Alden Quick Mart Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00005-2024UPG Upgrade Approved / Issued 1/3/2024 1/3/2024 7/3/2024 Documents

Deficiencies (Current)

NOV Number: E0020240995 (Pending)    Issue Date: 4/4/2024    Expiration Date: 6/3/2024    View NOV Form

Tanks Deficiency
Facility Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Section 175.210g; All dispensing units shall be readily visible from the control station without assistive devices. If view is permanently obstructed, or the dispenser is located so that activity is not readily visible, closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station may be used. are not visible from Control Station. In lieu of cameras, Remove impediments from windows or install remote cameras to monitor dispenser activity.

NOV Number: E0020240996 (Pending)    Issue Date: 4/4/2024    Expiration Date: 6/3/2024    View NOV Form

Tanks Deficiency
3 Precision tank test required. - Precision tank test is required on tank(s) if you cannot provide 24 months’ worth of tank “PASS” from ATG.
3 Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG. Must maintain 24 months’ worth. After Precision tank test you must maintain your leak detection and provide monthly tank "PASS" from the ATG. Failure to maintain passing results every month, will require an upgrade of the automatic tank gauge in the future. Annual tank tightness testin is NOT a leak detection option.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
00-0849 Eligible 1/22/2003 2/14/2003 $15,000
92-2962 Eligible 2/1/2010 2/17/2010 $15,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 2000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/20/1992
OSFM First Notify Date: 9/28/1989 Abandoned Material:
Current Age: 15 Abandoned Date:
Install Date: 1/1/1977 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 2000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/20/1992
OSFM First Notify Date: 9/28/1989 Abandoned Material:
Current Age: 15 Abandoned Date:
Install Date: 1/1/1977 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/7/1992 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 10/23/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/24/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 2/14/2024 2/14/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/14/2024 2/14/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 2/14/2024 2/14/2025
Overfill Prev Device Overfill Drop Tube Valve 3/4/2024 3/4/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Double Wall Spill Bucket 1/11/2024 1/11/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 2/14/2024
Tank STIP3 Single Wall Precision Test (Tank) Pass 12/18/2020



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/7/1992 Abandoned Material:
Current Age: 31 Abandoned Date:
Install Date: 10/23/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/24/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 2/14/2024 2/14/2027
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 2/14/2024 2/14/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 2/14/2024 2/14/2025
Overfill Prev Device Overfill Drop Tube Valve 2/14/2024 2/14/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 2/14/2024 2/14/2027
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test Pass 2/14/2024
Tank STIP3 Single Wall Precision Test (Tank) Pass 12/18/2020

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A

MFD Motorfuel Dispensing Forms