Deficiencies (Current)
NOV Number:
E0020240995
(Pending)
Issue Date:
4/4/2024
Expiration Date:
6/3/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Attendant does not have means to remotely monitor or no emergency shutoff switch 20' to 50' from dispenser - Section 175.210g; All dispensing units shall be readily visible from the control station without assistive devices. If view is permanently obstructed, or the dispenser is located so that activity is not readily visible, closed-circuit cameras that provide a view of each side of the dispensing unit and project an image on a screen at least 6 inches in diagonal located at the control station may be used. are not visible from Control Station. In lieu of cameras, Remove impediments from windows or install remote cameras to monitor dispenser activity. |
NOV Number:
E0020240996
(Pending)
Issue Date:
4/4/2024
Expiration Date:
6/3/2024
View NOV Form
Tanks |
Deficiency |
3 |
Precision tank test required. - Precision tank test is required on tank(s) if you cannot provide 24 months’ worth of tank “PASS” from ATG. |
3 |
Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG. Must maintain 24 months’ worth. After
Precision tank test you must maintain your leak detection and provide monthly tank "PASS" from the ATG. Failure to maintain passing results every month, will require an upgrade of the automatic tank gauge in the future. Annual tank tightness testin is NOT a leak detection option. |