Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2023514
Status: Active
Facility Name: Quick Stop
Address: 264 Torrence Avenue
Calumet City, IL 60409
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002959
Green Tag Issue Date: 6/6/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Jaspreet Petroleum, Inc.
Owner Address: 264 Torrence Ave.
Calumet City, IL 60409
Owner Status: Current Owner
Purchase Date: 11/9/2005
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/10/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/6/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033891 Jaspreet Petroleum, Inc. Current Owner 11/9/2005
U0023353 R & B Corp. of NW Indiana, Inc. Former Owner 11/9/2005
U0023353 R & B Corp. of NW Indiana, Inc. Former Owner 4/11/1994
U0013081 Rolly Super Ser Inc Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240945 (Pending)    Issue Date: 4/1/2024    Expiration Date: 5/31/2024    View NOV Form

Tanks Deficiency
6, 7 Annual electronic line leak detector test not completed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shutoff switch form is available at https://sfm.illinois.gov. Perform test and complete form. Maintain form on site.
6, 7 Annual leak detection certification not completed (Required annually). - (ATG CERT.)
Facility Facility Operation and Maintenance Plan not completed or available. - Facility Operations and Maintenance Plan is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site.
6, 7 Line interstitial sensor functional test not accomplished (Required annually).
6, 7 Line interstitial sensors have been raised and rendered inoperational. - All dispensers.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
Facility Missing copy of emergency instructions or emergency procedures plan - Form is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site.
Facility Missing list of designated Class A/B & C Operators - Form is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site.
6, 7 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. Must maintain 24 months’ worth. (Liquid Status)
6, 7 Piping interstitial must be open in all sumps - Remove jumper tubing and/or Schrader valves in all STP and all dispenser sumps.
6, 7 Precision line test required. - Due to missing monthly passing tapes. (Liquid Status)
6, 7 Required monthly tank interstitial sensor records not available. - Maintain one NORMAL report per TANK, per month, from ATG. Must maintain 24 months’ worth. (Liquid Status)
6, 7 Required monthly tank leak test records not available. - Maintain one PASSING report per TANK, per month, from ATG. Reference 175.630 c)2)B) (CSLD Results)
6, 7 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Shear valves/Impact valves. Provide documentation that annual testing of all shear valves has been conducted and passed. Go to https://sfm.illinois.gov to print out the Shear Valve inspection form.
6, 7 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
6, 7 Tank monitor does not appear to function properly and requires maintenance. - Indicator light(s) on panel of Veeder-Root ATG is/are not functional. Replace as necessary to provide proper operation. (Green and Yellow)
6, 7 Tank precision test required. - Due to missing monthly passing tank leak test records.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
14-0788 8/20/2014 Removal Log 00682-2014REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
14-0788 Eligible 8/29/2014 10/22/2014 $5,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 6000 Gasoline Removed Federal $0.00 08/19/2014 - REM
2 6000 Gasoline Removed Federal $0.00 08/19/2014 - REM
3 6000 Gasoline Removed Federal $0.00 08/19/2014 - REM
4 6000 Gasoline Removed Federal $0.00 08/20/2014 - REM
5 6000 Gasoline Removed Federal $0.00 08/20/2014 - REM
6 10000 Gasoline - Regular Currently in use Federal
7 5000 Gasoline - Premium Currently in use Federal

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active

MFD Motorfuel Dispensing Forms

No Forms Found