Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2023475
Status: Active
Facility Name: Kedzie Citgo, Inc.
Address: 11501 S. Kedzie Ave.
Merrionette Park, IL 60803
County: Cook
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: X002874
Green Tag Issue Date: 11/16/2022
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Kedzie Citgo, Inc.
Owner Address: 908 Pfingston Rd.
Glenview, IL 60025
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 12/23/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 11/16/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038875 Kedzie Citgo, Inc. Current Owner
U0032996 Abraham, Nimimon Former Owner 5/3/2004
U0031113 TGS New Enterprises, Inc. Former Owner 6/17/2002
U0022854 Kean Bros Inc Former Owner 10/25/1994
U0000018 1St Natl Of Evergreen Park Atu Former Owner 12/31/1967
U0027042 TGS New Enterprises Limited, LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020240824 (Pending)    Issue Date: 3/19/2024    Expiration Date: 5/18/2024    View NOV Form

Tanks Deficiency
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h)

NOV Number: E0020240825 (Pending)    Issue Date: 3/19/2024    Expiration Date: 5/18/2024    View NOV Form

Tanks Deficiency
Facility Facility Operation and Maintenance Plan not completed or available. - Facility Operations and Maintenance Plan is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site.
8 Install or replace lockable fill pipe caps. - Regular snap cap is missing it's gasket. Repair/Replace
6, 8, 9 Line interstitial sensor functional test not accomplished (Required annually). - All Dispenser and Tank top sump sensors need to be tested for positive shut down.
6, 8, 9 Line interstitial sensors have been raised and rendered inoperational. - All dispenser and Premium STP.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov.
Facility Missing copy of emergency instructions or emergency procedures plan - Form is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site.
Facility Missing list of designated Class A/B & C Operators - Form is available at https://sfm.illinois.gov to download and complete. Maintain documentation on site.
6, 8, 9 Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. Must maintain 24 months’ worth. (Liquid Status)
6, 8, 9 Piping interstitial must be open in all sumps - Dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. 175.420 b)
6, 8, 9 Precision line test required. - Due to missing monthly passing tapes and raised sensors.
6 Required monthly tank leak test records not available. - Maintain one PASSING report per TANK, per month, from ATG. Reference 175.630 c)2)B)
8, 9 Tank monitor does not appear to function properly and requires maintenance. - ATG in alarm; repair/replace as necessary to secure alarm. (L5 Alarm Out Alarm)
6 Tank precision test required. - Required due to missing monthly tank leak test records.
6, 8, 9 Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Dispenser sumps 1-8 and 11/12.
6, 8, 9 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - All Dispensers.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
16-1157 1/26/2017 Abandonment Log 00064-2017ABN
93-2921 7/28/1994 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
93-2921 Eligible 5/16/1994 6/10/1994 $15,000
20110972 Eligible 8/22/2017 8/24/2017 $5,000 Letter
20161157 Eligible 8/22/2017 8/31/2017 $5,000 Letter
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 6000 Diesel Fuel Removed Federal $0.00 07/28/1994 - REM
2 10000 Gasoline Removed Federal $0.00 07/28/1994 - REM
3 10000 Gasoline Removed Federal $0.00 07/28/1994 - REM
4 550 Used Oil Removed Federal $0.00 07/28/1994 - REM
5 1000 Heating Oil Removed State $0.00 07/28/1994 - REM
6 10000 Diesel Fuel Currently in use Federal $0.00
7 2000 Kerosene Abandoned in place Federal $0.00 01/26/2017 - ABN
8 12000 Gasoline - Regular Currently in use Federal $0.00
9 8000 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
11/12 Active
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active

MFD Motorfuel Dispensing Forms

No Forms Found